- Check the power supply wiring.
- Check whether the power supply voltage meets the specifications.
- For Pt100 input specifications, connect a 100 Ω resistance between input terminals A and B, short the B terminals, then confirm that the output is equivalent to 0°C.
- If the output signals is of the current specifications, attach an external 250 Ω resistance and measure the voltage.