I'm using dedicated DX communication commands to communicate with the Mitsubishi MELSEC. The first command is accepted, but I get no response from any subsequent command (even the same one as the first command). What could be the problem?

Some commands are sent in units of words. This always results in an even number of bytes. But if you send the command "FD0,1,1CRLF", for example, that is an odd number of bytes (9), and the 10th byte which follows CRLF will be populated with "junk." This junk byte becomes the 1st byte of the subsequent command, making it unintelligible. Try inserting a space as in "FD0,1,1spCRLF," to make it an even number of bytes.

Gerelateerde producten & oplossingen

  • Button Operated DX1000/DX2000

    The Daqstation DX1000/2000 series is a data acquisition system with display. Its HMI supports custom graphics for industry applications, audit trail and advanced security conforming to FDA 21CFR Part 11.

    Meer
  • Removable Chassis DX1000N

    The DX1000N features a removable chassis via the front panel of the instrument. This allows easy access and maintenance of internal components of the DX1000N.

    Meer

Top