Introduction & Process Overview
Package boilers require less fuel and electric power to operate and are widely used in the pharmaceutical, food, ceramic, and other industries. A package boiler operates more efficiently if the oxygen concentration in the flue gas is reduced. On the other hand, insufficient air intake causes incomplete combustion, resulting in increased smoke emission. Optimizing air intake for boiler operation requires continuous measurement of the oxygen concentration in the flue gas.
The typical package boiler is a water tube boiler or flue and smoke tube boiler with a capacity of 5 to 20 t/h (average steam generation capacity). The most widely used fuels are heavy oil, light oil, kerosene, and gas.
The ZR22G/ZR802G zirconia oxygen analyzer is ideally suited for package boilers thanks to its long service life and low maintenance, and is an effective tool for the reduction of fuel and electric power consumption.
Expected Benefits
- Increases combustion efficiency of package boilers
- Stable, continuous measurement
- Reduces operating cost
- Keeps the initial cost of equipment replacement to a minimum
Solution Details
Process Conditions
Measuring point | Boiler outlet, economizer outlet |
---|---|
Temperature | 150 to 300 °C |
Flow Velocity | 15 m/s max. |
Pressure | ±0.5 kPa |
Dust | 1 g/Nm3 max. |
Effectiveness in Saving Energy
A 1% reduction in excess oxygen of flue gas realizes a 0.8% saving in fuel.
Measurement system
Detector | ZR22G-☐☐☐-S-☐-☐-☐-☐-E-A/☐ |
---|---|
Converter | ZR802G-☐-☐-N-N /☐ |
Flow setting unit | ZA8F-☐*C |
Dust guard protector | K9471UC |
Utilities
Rated voltage | 100 to 240 V AC |
---|---|
Rated frequency | 50/60 Hz |
Power consumption | 330 VA (Max. 800 VA) |
Instrument air | 300 to 700 kPa |
Notes on Installation
- The detector should be mounted 2 to 3 m away from the boiler outlet.
- Typical good/bad installation examples are shown in Figure 1.
Special Notes
- The ZR22G/802G zirconia oxygen analyzer can also be used in bagasse- or bark-fired boilers under general conditions.
- Use of VVVF control can yield further reductions in fuel and electric power consumption. This can be done by combining the zirconia oxygen analyzer with a VVVF inverter and a programmable controller.
Figure 1 Instructions for Installation
Industrien
-
Power
In the mid 1970s, Yokogawa entered the power business with the release of the EBS Electric Control System. Since then, Yokogawa has steadfastly continued with the development of our technologies and capabilities for providing the best services and solutions to our customers worldwide.
Yokogawa has operated the global power solutions network to play a more active role in the dynamic global power market. This has allowed closer teamwork within Yokogawa, bringing together our global resources and industry know-how. Yokogawa's power industry experts work together to bring each customer the solution that best suits their sophisticated requirements.
-
Thermal
Thermal power using coal, oil or gas as fuel accounts for the majority of electric generation throughout the world.
Zugehörige Produkte & Lösungen
-
Zirkonia-Sauerstoff-/Feuchtigkeitsanalysator ZR22G, ZR802G
Dieser Analysator zur Messung der Sauerstoffkonzentration und Luftfeuchtigkeit bei hohen Temperaturen besteht aus einem Detektor ZR22G, der mit einem langlebigen und äußerst zuverlässigen Zirkonia-Sensor ausgestattet ist, und einem Messumformer ZR802G, der über digitale Kommunikations- und Datenprotokollierungsfunktionen verfügt.
Messungen mit ZR22G und ZR802G sind direkt und kontinuierlich ohne Probenahmegerät möglich. Die Geräte sind besonders wartungsfreundlich ausgelegt. Durch eine umfangreiche Selbstdiagnose der Sensorverschlechterung (ohne Einsatz von Kalibriergas) und der Möglichkeit des Austausches des Heizelements vor Ort können effektiv Betriebskosten eingespart werden. -
Sauerstoffanalysatoren
Sauerstoffanalysatoren liefern wertvolle Messwerte, beispielsweise für die Regelung von Verbrennungsprozessen, die Einhaltung der Prozessqualität, die Gewährleistung der Prozesssicherheit und Emissionseinhaltung.