Ex. 1 Using alarm settings and an AND relay
Input channel alarm settings
- Level1=H
	
- Alarm value=100.0 (°C)
 - Relay (internal SW) setting = Output relay number
 
 - Level2=L
	
- Alarm value=500.0 (°C)
 - Relay (internal SW) setting=Output relay number
 
 
Set the relay output number of the specified output relay to AND (Setup mode)
Ex 2: Using the general-purpose MATH function (with the /M1 option)
If the input channel is 001
- Formula:
(001.GE.K01)AND(001.LE.K02) -----GE, LE, and AND are operators (for details, see the user's manual) - MATH constants:
K01=100.0(°C)
K02=500.0(°C) - MATH ch alarms:
	
- Level1=H
		
- Alarm value=1
 - Relay (internal SW) setting=Output relay number
 
 
 - Level1=H
		
 
The setting of the relay output of the specified output relay number is OR (initial value)
Gerelateerde producten & oplossingen
- 
							
DA100-1
Model Name: DA100-1
 - 
							
DA100-2 Portable Hybrid Recorder
DA100-2 Portable Hybrid Recorder