How can the SA11 be connected to the terminals of the UM33A-S?

Please see the drawing below of the terminal arrangement of the UM33A-S.
To guarantee EMC- and Common Mode noise behavior of SA11, the FG terminal (#306) must be interconnected to Power supply Earth terminal (#112) by separate wire.
Use WU11-S type cable only, NOT WU11-V type cable. The WU11 cable can be connected directly to UM33A terminals.

UM33A-S: Terminal arrangement