TC10 Temperature Controller

The TC10 is a compact single loop temperature controller with an easy-to-read 3-color LED display. The shallow depth of the controller helps save to space. The TC10 supports easy configuration with codes for quick start-up.

Main Features

  • Compact size: 48 x 48 mm (1/16 DIN), depth of 48 mm + 14 mm (terminals)
  • 3 Dynamic Colors Led Display
  • Universal input: (TC, mV, V, mA, Pt100-Pt1000)
  • 4 Set Points and alarm functions
  • Serial communication : RS-485 Modbus
  • PID control, ON/OFF, Auto-tuning
  • IP65 front panel (when the optional panel gasket is mounted)(optional)

UT35A/UT32A

The UT35A and UT32A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT35A/UT32A also support open networks such as Ethernet communication.

Mid-level UT55A/UT52A

The UT55A and UT52A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT55A/UT52A also support open networks such as Ethernet communication.

【Support Information】New Legislative Framework (NLF) Conforming Products

This is a list of recorder and controller products that support the New Legislative Framework (NLF.)

The SP value is not displayed if you don’t specify a control operation. Assign OP4 to the control output operation.
On burnout, it will be 0 mA. There is no parameter for specifying the output direction.
AL on the front of the TC10 is the alarm lamp. 1 to 4 indicate the status of outputs 1 to 4.
Approximately 2 seconds or less. (63% response when the input changes from 10% → 90%)
Pt100: 150 μA Pt1000: 15.5 μA
No, they’re clamp terminals.
What is the TC10’s warranty period?
(ns-faq-ut-2253-other)
18 months (a year and a half) after shipment from the factory.
Yes, by changing the DP setting from 0 to 1. When you do this, the upper limit range of 1000°C becomes 999.9°C.
How many analog outputs are there?
(ns-faq-ut-2204-spec)
There is 1 analog output.
Yes. Set DISP to nonE.
Set detailed parameter out group o1.F (output 1 function) = r.inP.
Yes. Reffer to Specifications
Yes, if the input type is voltage or current.
Can I initialize parameters on the TC10?
(ns-faq-ut-2225-setting)
Yes. On the PASS screen, set “-481.”

Looking for more information on our people, technology and solutions?


Contact Us
Top