Oxidation Monitoring in the Cyanide Wastewater Treatment Process

Download (171 KB)

Oxidation Monitoring in the Cyanide Wastewater Treatment Process

Cyanide decomposition process
Cyanide decomposition process

Cyanide-bearing wastewater from mining and electroplating facilities and certain types of chemical plants is toxic and must be treated by oxidation with chlorine or chloride to bring the cyanide concentration within regulatory limits. The waste materials contain alkaline, rare earth metals, and other heavy metals such as iron, nickel, zinc, cadmium, copper, silver and gold. As well as sometimes can contain the deadly poison, cyanide. As the speed of the oxidation reaction is closely tied to the pH value, a pH analyzer is used together with an ORP (oxidation-reduction potential) analyzer to monitor the completion of the reaction. The use of these analyzers also ensures that excessive amounts of chemicals (e.g., chlorine) are not used to produce the reaction. Both 2-wire and 4-wire analyzers are suitable for this measurement system. A gold electrode should be used for ORP measurement of cyanidecontaining solutions.

Expected Benefits

  • Measures pH/ORP of cyanide wastewater continuously
  • Reduces operating costs

Process Overview

Measurement of ORP

Cyanide decomposition takes place in two stages. In the primary reaction, cyanide is oxidized to cyanate under high alkaline conditions (high pH and ORP). In the first reaction tank, the pH of the waste is measured and caustic (NaOH at 50% strength) is injected to raise the pH to 10 or higher. The oxidation reduction potential (ORP) of the waste is measured, and chlorine gas (Cl2) is automatically injected to raise the ORP to 400 mV or higher. The reaction normally occurs within 5 to 10 minutes.

In the secondary reaction, the cyanate is further oxidized under near-neutral conditions and converted to harmless carbon dioxide and nitrogen gases. In the second reaction tank, the pH of the waste is measured, and acid is injected to lower pH to 7-8. This process takes 2 to 5 minutes. In the third reaction tank, the ORP of the waste is measured and chlorine gas (Cl2) is automatically injected to raise the ORP to 600 mV or higher (Meanwhile the pH controller maintains the set-point at 7-8, correcting for any acidity created by the addition of the chlorine gas). This reaction occurs, taking 10 to 15 minutes, then the cyanide is eventually converted to harmless materials by the above reaction and the waste can be discharged.

 

  

Solution Details

Measurement system
2-wire/4-wire ORP measurement system
2-wire/4-wire pH measurement system
Sensor
KCl refillable ORP sensor: OR8EFG-AU-☐☐-TT1-☐*A
KCl refillable pH sensor: PH8EFP-☐☐-TN-TT1-N-☐*A
Submersion type holder: PH8HS-PP-☐☐-T-NN-NN*A
Terminal box (when needed)
WTB10-PH1 (for 2-wire system)
WTB10-PH3 (for 4-wire system)
Converter/transmitter:
2-wire transmitter (pH/ORP): PH202G-E-E
4-wire pH/ORP converter: PH450G-A-☐
Distributor (for 2-wire system): PH201G- A☐*B

Measurement Conditions

A gold electrode should be used to ensure accurate measurement of ORP in cyanide solutions. When the potential is near or under 200 mV during the cyanide oxidation process, a platinum electrode produces a catalytic reaction that causes hydrogen to form on the electrode surface. This generates potential and affects measured values.

pH and ORP levels in this area can be simultaneously monitored with the PH450 pH/ORP Analyzer. The model PH450 pH/ORP Analyzer performs continuous sensor diagnostics to notify the user when the sensor is coated or the glass electrode has broken.

The PH20 "Tempress" sensor with has a 3/4" NPT threads is convenient to install and use in the reaction tanks. Adapters enable it to be converted into a 1" MNPT thread, as well as a flow thru assembly or direct insertion assembly with a cleaning system. This sensor features four separate elements (pH, reference, temperature, ORP) in a rugged PVDF body. The integral number-coded cable and integral NPT threads allow for easy and convenient installation. When used with PH4050 or PH202 pH/ORP Analyzers, it can give simultaneous measurements of pH and ORP is possible with one sensor.

Utilities

PH202G
Power supply: 17 to 40 V DC (from distributor)
PH450G
Power supply: 96 to 264 V AC, 50/60 Hz
Power consumption: approx. 15 VA
PH201G distributor
Power supply:

100 V: 20 to130 V DC/80 to 138 V AC, 47 to 63 Hz

220 V: 120 to 340 V DC/138 to 264 V AC, 47 to 63 Hz
Power consumption: 24 V DC: approx. 200 mA
100 V AC: approx. 7 VA
220 V AC: approx. 11 VA

Industrien

Zugehörige Produkte & Lösungen

2-Leiter-Analysator FLXA202/21

Die Analysatoren der FLEXA-Serie werden für kontinuierliche Online-Messungen in industriellen Anlagen verwendet. Mit der Option für die Ein- oder Zwei-Sensor-Messung sind sie die flexibelsten 2-Leiter-Analysegeräte auf dem Markt.

4-Leiter-Leitfähigkeitsanalysator

Die Serie EXAxt450 deckt alle Leitfähigkeitsanwendungen, einschließlich aller speziellen Softwarefunktionen, bereits mit den Standardanalysatoren ab. Dies reduziert die Anzahl der Konfigurationen. Das bedeutet weniger Inventar und weniger Schulungsbedarf für Benutzer, die mit mehreren Leitfähigkeitsanwendungen arbeiten.

4-Leiter-pH/ORP-Analysator PH450

Der pH- und ORP-Analysator PH450 ist ein multivariabler Analysator, der pH- mit Temperatur- und ORP (Redox)-Messung kombiniert. Diese Messungen können über verschiedene Ausgangsfunktionen genutzt werden: zwei Stromausgänge, vier unabhängige SPDT-Kontaktausgänge und HART. 

Digitaler SMART pH/ORP-Universalsensor FU20F

Digitaler SMART-Kombinationssensor für pH und ORP nach dem Motto „einfach ist am besten“ mit eingebauter Intelligenz und direkter digitaler Kommunikation. 

Durchfluss/NPT-Armaturen FF20/FS20

Yokogawa hat viel Aufwand und Zeit in die Entwicklung einer breiten Palette von Armaturen investiert. Ein besonderer Schwerpunkt lag dabei auf der Senkung von Installations- und Wartungskosten und somit günstigeren Betriebskosten.

pH/ORP-Universalsensor der Serie FU20/FU24/PH20

Die Universalsensoren PH20, FU20 und FU24 für pH und ORP (Redox) zeigen, wie Yokogawa das Motto „einfach ist am besten“ auf Sensortechnologie anwendet.

pH- und ORP-Analysatoren

Sensoren und Analysatoren für pH und ORP (Redox) werden zur kontinuierlichen Überwachung von pH- und ORP-Werten im Prozess eingesetzt, z.B. um die Wasser- und Produktqualität sicherzustellen oder um Abflüsse, Batch-Neutralisierung, Zellstoffbestand, Gaswäscher, Kühltürme, chemische Aufbereitung, Wasser- und Abwasserbehandlung und viele andere Anwendungen zu überwachen.

pH- und ORP-Sensoren

pH-Elektroden und -Sensoren sind die detektierenden Elemente bei der Messung des pH-Werts. Die verschiedenen Installationsoptionen schließen u. a. Wechsel-, Durchfluss- und Eintaucharmaturen sowie den direkten Einbau ein. Die richtige Auswahl von pH-Elektroden und Sensoren ist für optimale Messergebnisse von entscheidender Bedeutung.

×

Have Questions?

Contact a Yokogawa Expert to learn how we can help you solve your challenges.

 
Top