I set the scan interval to 1 s and the recording interval to 10 s with SMARTDAC+ GX/GP series. Is the computation interval the same as the scan interval (1 s)? Or is it the recording interval (10 s)?

Computations are performed at the scan interval. The computation interval will be 1 s.