Measurement of O2 Concentration in Hot Blast Stoves

Download (261 KB)

Introduction

Hot Blast Stove Process
Hot Blast Stove Process

Measurement of O2 Concentration in Hot Blast Stoves Essential to Improving Combustion Efficiency

In a hot blast stove, the by-product gas produced in a coke oven is burned to preheat the air blast for the blast furnace. To improve the combustion efficiency and conserve energy in a hot blast stove, it is essential to be able to control combustion by measuring and adjusting the oxygen concentration in the exhaust gases.

The ZR22/ZR402 Direct In-Situ Zirconia Oxygen Analyzer is ideally suited for combustion control in hot blast stoves. It utilizes a long life sensor.

Expected Benefits

  • Improves combustion efficiency in hot blast stoves
  • Ensures stable, continuous oxygen measurement
  • Reduces operating costs
  • Minimizes the need for equipment replacement

Process Overview

The temperature of the hot blast used in blast furnaces has been increasing every year and currently stands at around 1300°C. Under such circumstances efficient operation is achieved by such measures as increasing the calorie value of fuel gas, replacing the hot blast stoves more frequently, and recovering waste heat from gas. To further improve combustion efficiency and save energy, measurement of the oxygen concentration in exhaust gases is required.

Solution Details

Field Data

Process Conditions

Measurement point: duct
Temperature: 20 to 350°C
Pressure: 3.5 to 10 kPa
Dust: 50 mg/Nm3
Fuel: Gas

Measurement System

Detector: ZR22G-015-S-Q-E-☐-☐-E-A/CV/Z
Z: Glove box option
Converter: ZR402G-☐-E-E-A
Flow setting unit: ZA8F-☐*B

Calibration gas unit

Pressure regulator for gas cylinder: P/N G7013XF (inlet W22, outlet Rc1/4) or
P/N G7014XF (inlet W22, outlet 1/4NPT)
Case assembly for calibration gas cylinder: P/N E7044KF

Note: the calibration gas cylinder must be purchased locally

Utilities

Power supply: 85 to 264 V AC, 50/60 Hz
Instrument air (reference gas): pressure, 300 to 700 kPa

Notes

  • The detector is installed in a glove box to reduce the sample gas pressure.
  • When more than three detectors are installed, it is recommended that the AV550G Averaging Converter be used instead of the ZR402G converter. The AV550G accepts signals from up to eight detectors.

Solution Details

Industries

Related Products & Solutions

Multi Channel Oxygen Analyzer System ZR22/AV550G

The AV550G multi channel oxygen analyzer system allows for measurements on up to 8 ZR22 probes simultaneously.The ZR probe's in-situ measurement method does not require any process conditioning or extractive sampling. This reduces maintenance costs and allows faster measurement response to changes in the process.

Single Channel Oxygen Analyzer System ZR22/ZR402

The ZR probe's in-situ measurement method does not require any process conditioning or extractive sampling. This reduces maintenance costs and allows faster measurement response to changes in the process.

Oxygen Analyzers

Oxygen analyzers provide valuable measurements in combustion control, process quality, safety and environmental applications.

×