Even in the YS1350 and YS1360 Cascade mode (C mode), the output value of the MV does not follow the value of the cascade input (X2) . How do I output the value of the cascade input on the MV?

To output the cascade input (X2) during cascade operation, set the setting value of CONFIG2 > CMOD1 to CAS.

Note: The default value for CMOD1 is "-".


Top