My voltage and current measurements on the power monitor are correct, but power integration either doesn't occur, or the values are small. How do I check whether the measured values are abnormal?

Check the active power. If the active power turns negative or extremely small, check the items below. The active power is negative when the power is regenerating.

Active power check items

Items to check

  1. Is the CT attachment orientation correct?
  2. Is a CT connected to the R and T phases?
  3. Is the R phase CT connected to 1S and 1L, and is the T phase CT connected to 3S and SL? Also check the polarity (k, l) on the CT secondary side.
  4. Are R, S, and T wired to P1, P2, and P3?

Check the wiring and attachment for other phase and wiring schemes as well.

Related Products & Solutions

  • PR201 Power Monitors

    The PR201 Power Monitors was discontinued on 1/01/2006. The PR300 is a replacement product.

  • UPM100/UPM101

    UPM100 / UPM101 представляет собой компактное устройство контроля электрических характеристик, способное измерять 15 параметров с помощью одного прибора.

  • UZ005 Power Monitors

    The UZ005 Power Monitors was discontinued on 9/01/2006. The PR300 is a replacement product.

  • Комплекcная система мониторинга потребляемой мощности SMARTDAC+ GM / UPM100

    Комплексная система мониторинга потребляемой мощности SMARTDAC+ GM/UPM100 – это система сбора данных для мониторинга энергосбережения, состоящая из монитора мощности UPM 100, совместимого с частотой 920 МГц, и системы сбора данных GM. Комплектная система обеспечивает визуализацию (графическое представление) потребления электроэнергии на предприятиях, составление отчетов и другие функции, помогающие определить области нерационального использования энергии


Наверх