How can I use control relay output as an alarm relay (alarm 4)?

As an example, we describe how to use Control relay as Alarm output 4 (Deviation low limit).

1. Setting Setup Parameter
  1-1. Set OT(Output type selection) to other than OT=00.03
       ex) OT=00.02 (Current Output)
  1-2 Set OR.S (OUT relay function selection) to 4357 (Alarm 4)

2. Setting Operation Parameters
  2-1. ALRM (Alarm function) 
       Set AL4 to 0.0.0.06 (Deviation low limit), and set HY4
  2-2. SP (SP and alarm setpoint)
       Set A4 (Alarm-4 setpoint)
       ex) 1A4=-10.0

Related Products & Solutions

  • Advanced Application UT75A

    The UT75A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT75A also support open networks such as Ethernet communication.

    See More
  • Mid-level UT55A/UT52A

    The UT55A and UT52A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT55A/UT52A also support open networks such as Ethernet communication.

    See More
  • UP55A

    The UP55A is a newly-released 1/4 DIN sized program controller provides up to 30 program patterns, and simultaneous monitoring of 8 PV events, 16 time events, and 8 alarms. Also a ladder sequence function is included as standard.

    See More
  • UT32A-D

    The UT32A-D is a compact digital indicating controller with selectable 2-loop control. It also includes a ladder sequence function.

    See More
  • UT35A/UT32A

    The UT35A and UT32A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT35A/UT32A also support open networks such as Ethernet communication.

    See More

Top