Outputting Messages When Monitoring with Gas Analyzers

Outputting Messages When Monitoring with Gas Analyzers (DX1000)

Using the Event Action Function

Remote input (BCD code) Formula Alarm Internal Switch Event Action
D01 D02 D03 D04
o       101=D01 H=1 S01 Message number 1
  o     102=D02 H=1 S02 Message number 2
o o     103=D01+D02 H=2 S03 Message number 3
    o   104=D03 H=1 S04 Message number 4
o   o   105=D01+D03 H=2 S05 Message number 5
  o o   106=D02+D03 H=2 S06 Message number 6
o o o   107=D01+D02+D03 H=3 S07 Message number 7
      o 108=D04 H=1 S08 Message number 8

Many messages can be output even with a limited number of remote inputs by combining the remote input, computation, alarm, and event action functions.

Eight different messages can be written by combining four remote inputs with eight internal switches.

  • D01–D04 are data types added with DXAdvanced, accepting remote input as contact input values.
  • S01–S08 are internal switches of functions added with DXAdvanced.
  • Alarms are represented with flags (internal switches) rather than relay output, and are set as "events" of the Event Action function.

Отрасли

  • Металлургия

    В отрасли металлургии крайне важно повышать качество не только продукции, но и технологий производства и эксплуатации, а также решать вопросы экологии и энергоэффективности. Компания Yokogawa помогает заказчикам в создании идеального предприятия, а также развивается вместе с ними ради совместного роста.

    Узнать больше

Related Products & Solutions

  • DX1000 / DX2000 с кнопочным управлением

    Серия Daqstation DX1000 / 2000 представляет собой систему сбора данных с экраном отображения данных. Интерфейс регистратора поддерживает пользовательскую графику для отраслевых приложений, журнал аудита и имеет расширенную безопасность к доступу данных в соответствии с требованиями FDA 21 CFR, Part 11.