What is the output during burnout for the DT5, DR5, DM1, and DS1?

The output behavior when the input is disconnected for the burnout setting is as follows.
All four models have a variable output range of -10 to 110% (-5% to 105% for the ±10 V range).
Therefore, the output at burnout is as follows.

  • For burnup, the output can be 110% or more (or 5.4 V or more for 1–5 V outputs).
  • For burndown, the output can be -10% or less (or 0.6 V or less for 1–5 V outputs).
  • For off, the output will be undefined, so it is unknown what will happen.

Related Products & Solutions

  • JUXTA D Series Signal Conditioners

    The D Series is DCS-supported signal conditioners, consisting of modular type signal converters with versatile I/O specifications and housing nest. JIS and EIA conformed mounting nests come with terminal blocks for field wiring, connectors for DCS connection, and connectors for communications.