Cell Voltage Monitoring Solution for Electrolyzer

Caustic soda and hydrochloric acid, produced in electrolyzer plants, are fundamental materials used in varieties of industries; chemicals, pharmaceuticals, petrol-chemicals, pulp & papers, etc. Proper control of the process brings you stabilized quality of products with the vast operational profit. Ion-Membrane electrolysis bath is the most effective among all types of electrolyzer in caustic soda production. A Membrane has life time. It should be maintained periodically. To prolong operating life, the electrolyzer plant should be monitored for optimized control.

Electrolytic Plant

Electrolysis Application

Caustic soda (NaOH) and Chlorine (Cl2) are generated by the electrolysis of Salt (NaCl). Electrolyzer is used to produce these fundamental materials.  The latest technology of this electrolysis system called “Electrolyzer” is used ion exchange membranes, and Ion exchange Membranes in electrolyzer is called "cell". An electrolysis bath is consisted of many cells. Cells are connected by series connection to each other. A Cell has life time, so it should be maintained periodically by monitoring the Cell Voltage.
There is a lot of cells in electrolyzer, so multi-channels data acquisition system is required to monitor the cell voltage. And Input channels of measurement instrument is appeared a few hundred voltage, so  the internal circuit of measurement instrument has to be isolated from external circuits for cell voltage monitoring, and data acquisition system with high withstand voltage is required.

Electrolysis Application

 

Electrolysis Application requirement

Multi-channel data logging

A Membrane used Ion-Membrane electrolysis bath has life time. The owner of electrolytic plant has to know each cell condition. The owner monitors each cell voltage to look at the cell condition. Each cell voltage is a few voltage (e.g. 3Vdc), but an electrolysis bath has a lot of cells (e.g. 100 cells or more), the maximum voltage may be a few hundred voltage (e.g. 300Vdc or more). Cell voltage monitoring for electrolysis bath is required multi-channel data logging system.

High withstand voltage to common mode signal with high voltage

Each cell voltage is small, but a few hundred DC voltage is appeared to both terminals (positive and negative terminal for each channel) of the last channels. It seems like a common mode signal that it’s appeared a few hundred voltage to both terminals. In this case, The internal circuit of measurement instrument has to be isolated by High withstand voltage to external circuit.

 

Solution for Cell Voltage Monitoring of Electrolysis Bath

Multi-channel data logging solution

GM10 can support the measurement of up to 420 analog input channels by using the GX90EX expansion module. Also the GM10-2 large capacity memory model can support the recording of up to 1,000 channels including MATH channels and Communication channels.

Modular style GM10 data acquisition system

Chain up to 6 subunits

High withstand voltage module

A few hundred DC voltage is appeared to both positive and negative terminal of a channel, so between internal circuit and external circuit of a measurement instrument has to be insolated. GX90XA-10-V1 analog input module with High withstand voltage can isolate between both circuits by 600Vrms/Vdc withstand voltage.

gx90xa/block diagram

Analog input module with High withstand voltage

  • Number of input: 10 channels per module
  • Input type: DC Voltage / Thermocouple / Digital Input
  • Common mode voltage for measuring input:
    600V ACrms / 600V DC

 

 

Отрасли

  • Химическая промышленность

    Химические производства применяют периодические и непрерывные технологические процессы производства, каждый из которых имеет свои особые требования для систем управления. Непрерывному технологическому процессу требуется надёжная и стабильно работающая система управления, защищающая от внеплановых остановов, в то время как для периодических процессов более важна гибкость организации партий, возможности внесения корректировок в рецепты и формулы. Для обоих типов процессов одинаково важно вести управление с поддержанием требуемого качества и способность управлять не рутинными операциями. Имея в наличии обширный послужной список и богатое портфолио проектов, а также опытных системных инженеров и обширную сеть поддержки по всему миру, у компании Yokogawa имеются решения для всех видов таких систем.

    Узнать больше

Related Products & Solutions

  • Модульный блок GM10

    Регистратор данных SMARTDAC + TM GM10 имеет модульную архитектуру, которая позволяет собирать необходимые данные. За счет поддержки не только ввода / вывода, но и многих протоколов связи, таких как беспроводная связь на частоте 920 МГц, Modbus и т.д. Мониторинг и изменение настроек доступны через Bluetooth. Соответствие требованиям FDA 21 CFR Part 11 и AMS2750E/NADCAP