Background Information
The core of the activated sludge process is primarily dependent on the control of the aeration basin. The most essential component of any activated sludge plant is the biomass, anaerobic and aerobic bacteria, that attaches themselves to the waste, and digest the waste resulting in relatively clean water as the by-product.
There are several types of bugs that are responsible for different duties. There are the carbon eaters (carbonaceous) and chemical eaters like ammonia (nitrogenous). Just like any other living organism they need certain conditions in order to sustain life and reproduce.
Introduction
Many components in a process must be in balance in order to obtain complete synergy; example biomass blends, air, return activated sludge (RAS), waste activated sludge (WAS) and throughput. The aeration basin is a holding and/or treatment pond that everything cycles through. It is essential to monitor and control several factors that can influence the efficiency of the biological conditions in the basin; for example:
Temperature: Normally the temperature will be between 10-40°C. Most biomass bugs achieve optimum efficiency in this range. Increasing or decreasing the temperature can result in the increasing or decreasing the rate at which the bugs eat and reproduce. Along with this all chemical reactions that are taking place at the same time are affected by the process temperature as well.
pH: For most systems the pH should be kept between 6.5 to 8.5 pH, when the pH is too high or too low, the biomass losses the ability to convert the food to energy and raw materials. A pH below 6.5 may cause the growth of fungi and fungal bulking, and will have to be adjusted using a caustic, lime or magnesium hydroxide.
Low Nutrients: If nitrogen and phosphorus are not presented in sufficient amount it can limit the growth rate of the biomass. A sign of nutrient deficiency includes foam on the aeration basin.
Dissolved Oxygen: DO is one of the most critical points of measurement; for most processes the target concentration will be between 1-3 mg/L. The concentration amount is an indication of the basin environment; whether it is in denitrification (excess nitrate, NO3) or nitrification (excess ammonium, NH4) environment. Essentially the DO measurement is set to a level to minimize the ammonium breakthrough. It is not uncommon to see NH4 and DO measurements together.
The DO measurement should be maintained at the point of greatest oxygen demand in the system. Normally this is near the intake portion of the aeration basin, because when the process is in the secondary clarifier no oxygen is added and the biomass bugs are starved of oxygen. When the process is returned to the aeration basin via the RAS pumps the biomass is returned to an oxygen rich area and the bug consume vast amounts of oxygen right away.
Septicity/Toxicity: Septic wastes contain elevated amounts of sulfides and organic acids (such as acetic acid). Other organic materials and heavy metals are also toxic to the biomass, reducing their efficiency or even destroying them.
Summary
Having too much oxygen in the process is not a problem for the biological system; however the cost for generating the oxygen is one of the largest expenses. By obtaining a good representative average of the dissolved oxygen present in the basin could save the plant large amounts of money. For this reason multiple measurements points are sometimes put into place.
Product Recommendations
pH:
Transmitter:
FLXA202/FLXA21 2-wire pH analyzer (intrinsic safety)
FLXA402 4-wire pH converter (general purpose)
Sensors:
FU20/FU24 Four-in-one pH sensor
Holders: (for FU20 sensor)
PB30 Floating Ball, when using S200256L8 adapter
Dissolved Oxygen:
Transmitter:
FLXA202/FLXA21 2-wire DO analyzer (intrinsic safety)
FLXA402 4-wire converter (general purpose)
Option #1:
Sensors:
DO30G Galvanic Sensor
Holders:
PB30 Floating Ball
FD30 Immersion Fitting
Option #2:
Sensors:
DO70G/DO71/DO72 Optical DO Sensor
Hamilton VisiFerm Optical DO Sensor
*Please note that an external 24 VDC power supply, like the Yokogawa DOX10, must be used with the sensor.
Holders:
PB30 Floating Ball *Available as special*
FD40 Immersion with K1523JA adapter
Industries
-
Water & Wastewater
Water resources are finite, and therefore contributing to a sustainable water cycle is one of the Sustainable Development Goals (SDGs). Yokogawa has been providing advanced digital control solutions for the stable supply of clean and safe water, wastewater treatment for protecting the water environment, water loss management and optimization of plant operation for reducing CO2 emissions and running costs. With our leading-edge technologies, dependable products and extensive expertise and experience of diverse water projects around the world, we work with you to provide sustainable water solutions that boost your business and add value throughout the plant lifecycle.
Yokogawa supports a wide range of water control applications in both the municipal and industrial water markets.
Related Products & Solutions
-
2-Wire Transmitter/Analyzer FLXA202
The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.
-
2-Wire Transmitter/Analyzer FLXA21
The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.
-
All-in-One pH/ORP Sensor Series FU20 and FU24
The FU20 and FU24, all-in-one pH and ORP, sensors show how Yokogawa applies the motto "Simple is best" to sensor technology.
-
Digital SMART SENCOM™ Adapter, SA11
Reusable SMART adapter, requiring only the analog sensor to be disposed of when it reaches the end of its lifetime. With the SENCOM 4.0 platform, Yokogawa delivers reduced costs and waste while contributing to its long-term business goals of a sustainable future for all.
-
Measuring Sensor DO30G
The DO30G sensor for dissolved oxygen is designed for use in water treatment plants such as sewage treatment works, effluent activated sludge process, and potable water treatment. It is also effective in river monitoring, intake protection, fish farming, and other fields where water quality is important.
-
Multi Channel 4-Wire Analyzer FLXA402
The FLEXA™ series analyzers are modular-designed analyzers used for continuous online measurements in industrial installations. They offer single or multi-sensor measurement.
-
Optical Dissolved Oxygen Sensors DO71/DO72
It is a fluorescent dissolved oxygen sensor that is easy to clean and stable for long term measurement. Sensor replacement is easy on site and reduces maintenance costs. It is possible to measure oxygen in a wide range including low concentration measurement.
Suitable for use in water treatment plants such as sewage treatment plants and wastewater treatment plants under severe measurement conditions.
Can be used in combination with FLXA402 liquid analyzer by digital communication. -
Dissolved Oxygen Sensors
Dissolved Oxygen (DO) electrodes and sensors are the sensing portions of a DO measurement. There are three common technologies for dissolved oxygen measurements: polographic, galvanic and optical. Various installation options including floating ball, retractable, flow thru, immersion, and direct insertion.
-
SENCOM™ SMART Digital Sensors
Yokogawa’s SENCOM SMART Sensor Platform is an innovative analyzer platform that optimizes maintenance, reduces configuration time, and simplifies in-field maintenance and calibration.