The UT35A and UT32A do not have an option for a heater break alarm in the Alarm Type settings (ALn). How do I use the heater break alarm on the UT35A/UT32A?

For the UT35A/UT32A to use the heater break alarm, configure the options in the HBA menu of the setup parameters.
For the UT350/UT351/UT320/UT321 of previous models, the Alarm Type (ALn) parameter can be set to the heater break alarm (Alarm Code: 24,25), but the UT35A/UT32A cannot.