YS1700 Boiler Control Overview

下載 (743 KB)

Overview

YS1700 Boiler Control Overview 1Automated control of industrial boilers is an excellent application for YS1700 microprocessor-based loop controllers. These instruments can be programmed to perform the operations of plant master, boiler master, fuel and air control with oxygen trim and drum level/feedwater control. Each of these control applications are discussed in this application note.

The YS1700 is a reliable and cost effective means of upgrading boiler controls and increasing boiler efficiency while lowering operating costs by implementing advanced control strategies. Although the functions of each controller discussed here differ, the YS1700 hardware platform is identical for each application.

Key features of the YS1700 include:

  • Dual PID loop capability
  • Built-in "Hard Manual" backup station
  • Two CPU design for reliability
  • LOOP, TREND & ALARM operator displays
  • Integral 24VDC transmitter power supply
  • Advanced self-tuning
  • RS485 & peer-to-peer communications options
  • Communication drivers for PLC's and SCADA/HMI software packages

Plant Master

Most industrial boilers operate on a header system. Steam is delivered to a header pipe by one or more boilers and is transferred from the header to the various process users. Pressure in the header is used as an indicator of the steam demand. A pressure transmitter is connected to the header and this signal is the process variable input to a YS1700 programmed as "Plant Master". This is a P+I controller that compares the pressure with an operator selected set point and computes a firing rate demand signal (output) to the combustion controls: {boilermaster(s) and the fuel/air controllers}.

Boilermaster

This controller accepts the firing rate demand signal from the Plant Master controller as the process variable. The output of boiler master provides the firing rate demand signal and operator applied bias to the fuel and air controllers for that specific boiler. This bias station allows the operator to select higher firing rates and therefore higher steam production from the more efficient boilers in a multiple unit configuration.

Additionally, discrete outputs from the fuel and air controllers provide mode status to the boilermaster controller. If the fuel or air controller is in MANUAL, the YS1700 programming logic can alert the boiler operator that the firing rate demand signal cannot be used in the combustion controllers.

A "Flame On" permissive from the burner management equipment alerts the boilermaster controller that the boiler can accept a firing rate demand signal and is not in a low fire, purge or off condition.

YS1700 Boiler Control Overview 2

Combustion Controls

The firing rate demand signal from the boilermaster controller(s) is used in the combustion control: fuel, air and flue gas percent oxygen. The YS1700 controller can be programmed to perform all these functions. In this text, the combustion control discussions will be limited to a single fuel with a parallel metered cross limited control configuration. The YS1700 controller can be programmed to select multiple fuels (e.g., oil or gas) or control a ratio of two combustibles.

The SAMA logic diagram below shows the interaction of the fuel and air controllers. The fuel and air flows are measured and compared to the firing rate demand signal. Low and high signal selectors are incorporated in the YS1700 programs to insure safe operation. The low selector in the fuel controller compares the firing rate demand signal and the air flow measurement and selects the lower signal as the set point. Inversely, the air controller compares the fuel flow measurement and firing rate demand signal selecting the higher as the air flow set point. Therefore, the fuel flow will not exceed the air flow. Function generators are applied to the outputs for characterization to the final control elements. A low limiter is configured into the air flow controller to prevent the air flow set point from being reduced less than 25% of full range. This minimum setting is required by NFPA code and insures safe operation during transmitter outage.

Discrete inputs and outputs are used for tracking the auto/manual status of the air controller. The fuel controller is forced to MANUAL if the air controller is placed in MANUAL. The fuel cannot be placed into the automatic mode until the air controller is returned to AUTO. This action is required to insure a safe and proper air/fuel ratio.

An auto/manual station can be used to generate a fuel/air ratio. For better combustion control and boiler efficiency, a flue gas percent oxygen analyzer and YS1700 controller can be incorporated into the air flow control strategy. The firing rate demand signal is modified by a function generator to calculate a load index. An operator applied bias can be applied to the index and this is the set point to the oxygen trim controller. The P+I output is adjusted for gain and bias (y=mx+b) and applied to the air flow measurement signal. High and low output limiters are used in the event of analyzer outage.

The YS1700 can be programmed to operate as a dual loop P+I+D controller. Therefore, the combustion air and percent oxygen controls can reside in one instrument. The YS1700 can display the measured variables (air & percent oxygen) on two different screens. Operator interface is simple and easy-to-read.

Feedwater Control

YS1700 Boiler Control Overview 3

The boiler feedwater controller is used to maintain the water in the steam drum at a desired set point. The intent is to replace each pound of steam taken from the steam drum with a pound of makeup water. A high drum level may allow water droplets to be carried over into the steam header and damage process equipment. A low level can cause damage to exposed tube surfaces.

A phenomenon exhibited in the steam drum is swelling and shrinkage. This is caused by the bubbles in the boiler tubes and the drum expanding and contracting. As the demand for steam is increased, the header pressure decreases and the master pressure controller increases the firing rate of the boiler(s). The associated decrease in drum pressure and higher firing rate causes the water bubbles to expand and the drum level increases. Conversely as the steam demand decreases, the header pressure increases and firing rate declines, causing collapsing bubbles and a lowering of the steam drum level. This action creates an opposite reaction in the feedwater controller. More feedwater is needed for higher steam flow, but as the level swells, the feedwater controller reduces the output to the valve. Using a drum level pressure transmitter and compensating for the change in drum pressure, the feedwater controller is not adversely affected. The drawing at the right shows a drum pressure measurement being applied through a function generator to the level input.

There are three types of boiler feedwater control configurations that are commonly supplied: single element (drum level only), two element (level & steam flow) and three element (level, steam & feedwater).

Single element control is commonly used in small boilers that are based loaded, i.e., little variation in steam demand. Changes in load are not incorporated into the control strategy.

Two element control uses a steam flow measurement as a feedforward element to change position in the feedwater valve. Changes in steam demand are sensed and adjustments to the valve are made. Varying feedwater pressure can change the flow rate and drum level. Fluctuating pressure is common in multi-boiler feedwater systems.

The SAMA diagram below shows a three element drum level control with pressure compensated drum level. The YS1700 controller is programmed in a cascade configuration, where the output of the drum level controller is linked to the remote set point of the feedwater flow controller. The steam flow measurement is applied to the output of the level controller to adjust the remote set point to the feedwater control proportional to varying steam demands. The secondary control is the faster reacting feedwater flow controller. Three element control is common on large boilers with varying load demands. This can be programmed into one YS1700, as a single station cascade controller with feedforward element and pressure compensated drum level.

Peer-to-Peer Communication

YS1700 controllers can be optionally provided with peer-to-peer communications. This feature permits data from one controller to be sent to another digitally over a single pair of twisted wires. Any controller parameter can be shared. Up to sixteen (16) controllers can be linked on this data network with custom configuration.

SCADA/HMI

Many boiler locations combine the control power and reliability of panel mounted controllers by linking their YS1700 controllers with popular SCADA/HMI software packages. Running such software in a personal computer provides advanced trending, alarming, operator graphics and other features while maintaining the boiler control functions in the YS1700's. Such a system provides features and functions similar to a Distributed Control System without the high price tag!

When using the RS485 communication option, sixteen (16) YS1700's can be linked to each communication port of the SCADA/HMI computer. The peer-to-peer option allows sixteen (16) controllers to "talk" with each other as the SCADA/HMI host computer accesses the network. The peer-to-peer option runs approximately eight times faster than the RS485 option (78,000bps vs 9600bps). Custom applications with up to 63 YS1700 controllers linked to a single PC communications port are possible when using the YS- Net peer-to-peer/PC network. Either YS1700 digital communication card discussed here can be provided at the initial purchase of the controllers or easily retrofitted in the field.

Summary

YS1700 - Boiler Control Solution
YS1700 - Boiler Control Solution

Using YS1700 loop controllers is an answer to upgrading aging or cumbersome boiler controls. Increased boiler efficiency and reduced operating costs can be realized. The programmability allows them to be used in a variety of applications. Discussions here have been limited to the most common boiler control applications. However, the YS1700 can be used for deaerator control, steam drum b treatment and a variety of auxiliary control applications in the industrial boiler domain.lowdown, condensate return, water treatment and a variety of auxiliary control applications in the industrial boiler domain.

Related Technotes

  • CP-A-04 - RS485 Communications/ Graphical User Interface Packages
  • CP-A-08 - YS1700 Peer-to-Peer Communications
  • CP-A-11 - Boiler Feedwater Control
  • CP-A-12 - Boiler Combustion Control

 

YS1700 Dual Loop Programmmable Controller

YS1700 Dual Loop Programmmable Controller

產業別

  • 大宗石油化工

    無論是生產石化產品、無機物還是中間產品,化工企業都面臨著成本和利潤率的壓力,必須及時有效地交付產品,同時保持安全合規運營。此外,化工企業必須應對原料和能源價格的波動,並為市場提供性價比最高的產品組合。

     

    橫河電機長期服務於全球大宗化工市場,得到大家的廣泛認可通製我們的產品、解決方案和行業專業知識,橫河了解您的市場和生產需求,並將與您合作,在您的工廠生命周期提供可靠、經濟的解決方案。

    更多
  • 水和廢水

    橫河電機通製開發更節能的技術,幫助減少運營的碳排放,以及構建保護環境免受污染的堅固建築,為可持續水生產提供控制解決方案。橫河憑借先進的技術和廣泛的應用專業知識與客戶合作,提供可持續水生產的解決方案,促進客戶的業務,並讓整個工廠在生命周期中增加價值。橫河的技術和產品可提高工廠的性能,確保它們在當今的水處理領域中具有競爭力,並降低運營成本。橫河支持市政和工業水處理領域的各種水控制方面的應用。

    更多

相關產品&解決方案

  • YS1310

    帶報警的YS1310指示器是一款輸入指示器,可以使用兩個輸入進行報警。可同時顯示2個回路。兩個輸入均可以生成上限報警、下限報警、上上限報警和下下限報警,並且可以從總共6個接點輸出任意報警的AND連接或OR連接。

    更多
  • YS1350/YS1360

    YS1350是一款手動設定裝定,可以手動輸出設定信號至控制器等設備。YS1360是一款手動設定裝定,可以手動輸出操作信號至操作終端。

    更多
  • YS1500

    YS1500指示控制器具有PID控制所需的基本控制功能。可以根據用戶用途選擇所需功能。

    更多
  • YS1700

    YS1700可編程指示調節器可以通製運行用戶程序為各種應用進行定制,並通製橫河電機的專有技術、用戶友好性和可擴展性提高可靠性。

    更多
  • 單回路控制器

    單回路控制器從傳感器接收溫度、流量、壓力和其他類型的測量讀數,並向閥門等控制元件發送相應指令,以便將這些值保持在期望範圍內。

    更多

置頂