There's no output with a pulse signal repeater and pulse rate converter. What should I do?

  1. Check the power supply wiring.
  2. Check whether the power supply voltage meets the specifications.
  3. Check the polarity of the input wiring.
  4. Check the pulse specifications of the other instruments.
  5. For voltage pulse, open collector, and non-voltage contact, check whether there is an external resistance connected to the input terminals.
  6. For current pulse, check whether the accessory resistor is connected to the input terminals. (some models may have built-in resistance, so be sure to check the specifications).
  7. Check the signal from the output terminal while using a clip or other conductor to open and short the (+) and (-) input terminals.
  8. You must apply external power to the output terminals (open collector / non-voltage contact AC switch). Check whether there is power.

相关产品&解决方案

  • JUXTA F Series Signal Conditioners

    F Series signal conditioners are compact, space-saving (24 mm width) signal conditioners with front panel terminals. The microprocessor based models provide field configuration capability and minimum stock of spares. The installation is either DIN-Rail, Rack or Wall mounting, and the power supply is 24 V DC.

    更多
  • JUXTA W Series Signal Conditioners

    Compact size, versatile mounting, and microprocessor based high performance capabilities makes the W Series an excellent choice for almost every application. The specifications of W Series signal conditioners are as same as F Series signal conditioners except for power supply voltage, second output and case width.