Industrial processes often employ multiple data acquisition systems to monitor the health of assets and facility infrastructure. These systems can be either standalone or built as nodes within a larger automation topology.

The GM10 is a scalable modular block I/O data acquisition system and data-logging platform that is designed for easy installation and maintenance and requires no programming.  It supports remote web-based or wireless configuration and monitoring via Bluetooth connection. The unit can be DIN rail mounted, wall mounted or act as a standalone desktop application. The Yokogawa GM10 delivers industry leading reliability and measurement accuracy. In addition, a wide range of communication protocols guarantee compatibility with your network architecture.

Main Features

Wide-ranging input/output specifications

  • The 10 channel universal input module measures DC volts, thermocouple, RTD, and contact input signals. A 16 channel digital input module and a relay output module are also available.            
    • GX90XA Analog input module: DC voltage, DC current, thermocouple, RTD, contact
    • GX90XA-04-H0 High Speed AI Module:[R4] New!  DC voltage, DC current, thermocouple, RTD, contact
    • GX90XA-06-R1 4-Wire RTD Module:[R4] New!  4-wire RTD, 4-wire resistance
    • GX90YA Analog output module:[R4] New!  Current output (Isolated between channels)
    • GX90XD Digital input module: Remote control input or operation recording
    • GX90YD Digital output module: Alarm output
    • GX90WD Digital input/output module: Remote control input or operation recording/alarm output
    • GX90XP Pulse intput module: Pulse signal data acquisition, integral count
    • GX90UT PID control module:[R4] New!  PID control (2 loop)

PID control  [R4] New!

  • Enables PID and program control (max. 20 loops per system)
  • The web application enables remote operation and monitoring from a browser.
  • Setpoint program control function (up to 99 patterns)

Dual interval measurement  [R4] New!

  • Users have the ability to choose two different scan intervals on a single GM system.

Scalability

  • Up to 420 ch per system
  • Plug and lock modules

Ease of Use

  • Web-based configuration
  • Live Web-based data viewing

Mobile Connectivity

  • Bluetooth
  • Mobile Application

Reliability

  • Secure data storage
  • High accuracy measurement
  • Automatic backfill function (GA10 Data Logging Software)

Noise Tolerance

  • Electromagnetic relay module

21 CFR Part 11 support (option)

  • Supports the U.S. FDA 21 CFR Part 11 (for pharmaceutical manufacturing).

Supports 12 to 28 VDC power

  • Supports 12 to 28 VDC power so you can also use it inside automobiles.

Multi-batch Function (option)

  • Recorder pre-defined channel groups to separate data files with independent start and stop control.

SLMP Communication (Mitsubishi PLC) (option)

  • Protocol function that enables connection from a GM to Mitsubishi Electric PLCs without sequence programs.

OPC-UA Server (option)

  • Data acquired by the GM can be accessed through Ethernet communication from a host system (OPC-UA client).

Aerospace Heat Treatment Supports heat treatment application AMS2750/NADCAP
Calibration correction schedule control function (option)

  • Schedule management for periodically executing calibration correction configuration and the like.

Ready for the future when you are

Increase channels by adding additional block modules

YOKOGAWA proprietary block architecture [Patent technology]

  • Expand one, or multiple module at a time
  • Unique design houses modules in linked module bases
  • Module base ensures linkage (slide locks and mounting screws also available)
  • Modules can be inserted and removed from the front panel for easy maintenance

YOKOGAWA proprietary block architecture

Names of data acquisition module parts

Names of data acquisition module parts

 

Comes standard with support for up to 100 ch of measurement (single-unit configuration)

Up to 10 I/O modules can be linked to a single data acquisition module (GM10)

Gm Image03

Installs anywhere

For the desktop, DIN rails, or wall-mounting. No special attachments required.

Gm Image04

Select from a wide range of I/O modules

Select modules according to your application. Noise-resistant, magnetic relay types also available. All modules have removable terminal blocks for easy wiring. The same modules used in the SMARTDAC+ series.

Select from a wide range of I/O modules

Model Name Measurement/Application Channels
GX90XA-10-U2 Analog input module DC voltage, DC current (with external shunt resistor connected), thermocouple, RTD, contact (solid state relay scanner type) 10
GX90XA-10-L1 DC voltage, DC current (with external shunt resistor connected), thermocouple, contact (Low withstand voltage solid state relay scanner type) 10
GX90XA-10-T1 DC voltage, DC current (with external shunt resistor connected), thermocouple, contact (electromagnetic relay scanner type) 10
GX90XA-10-C1 DC current (mA) (solid state relay scanner type) 10
GX90XA-04-H0 DC voltage, DC current (with external shunt resistor connected), thermocouple, RTD, contact (individual A/D type) 4
GX90XA-06-R1 4-wire RTD, 4-wire resistance(solid state relay scanner type) 6
GX90YA Analog output module Current output (isolated between channels) 4
GX90XD Digital input module Remote control input or operation recording 16
GX90YD Digital output module Alarm output 6
GX90WD Digital input/output module Remote control input or operation recording/alarm output DI:8/DO:6
GX90XP Pulse input module Pulse signal data acquisition, integral count 10
GX90UT PID control module PID control (2 loop) AI:2/AO:2
DI:8/DO:8

Analog input module scan interval and measurement type

Type Channels Scan interval
(shortest)
Scanner TC RTD DCV DI mA Resistance Feature
Universal (-U2) 10 100ms SSR     Universal
Low withstand voltage relay (-L1) 10 500ms SSR       Mid-price
Electromagnetic relay (-T1) 10 1s Relay       Noise-resistance
DC current input (-C1) 10 100ms SSR           mA only
High speed universal (-H0) 4 1ms     High speed measurement
4-wire RTD (-R1) 6 100ms SSR         4-wireRTD

Internal memory and max. I/O channels

Type Internal memory Max. input/output channels*
GM10-1 500 MB Single-unit configuration 0 to 100
Multi-unit configuration 0 to 100
GM10-2 1.2 GB Single-unit configuration 0 to 100
Multi-unit configuration 0 to 420

Actual values support high precision measurement

Input type Measuring accuracy*1 (typical value*2)
DCV 20 mV ±(0.01% of reading + 5 μV)
60 mV ±(0.01 % of reading +5 μV)
6 V (1-5V) ±(0.01% of reading + 2 mV)
TC*3 R ±1.1 °C
K ±(0.01 % of reading +0.2 °C) However, -200.0 to 0.0 °C :±(0.15 % of reading +0.2 °C)
K (-200 to 500 °C) ±0.2 °C However, -200.0 to 0.0 °C: ±(0.15 % of reading +0.2 °C)
J ±0.2 °C However, -200.0 to 0.0 °C: ±(0.10 % of reading +0.2 °C)
T ±0.2 °C However, -200.0 to 0.0 °C: ±(0.10 % of reading +0.2 °C)
N ±(0.01 % of reading +0.2 °C) However, -200.0 to 0.0°C: ±(0.22 % of reading +0.2 °C)
RTD Pt100 ±(0.02% of reading + 0.2 °C)
Pt100 (high resolution) ±(0.02% of reading + 0.16 °C)
*1 Applies to GX90XA-10-U2, A/D integration time 16.67 ms or more, General operating conditions: 23±2 °C, 55±10% RH, supply voltage 90-132, 180-264 V AC, power frequency within 50/60 Hz ±1 %, warm-up of 30 minutes or more, no vibrations or other hindrances to performance.
*2 For the measuring accuracy (guaranteed), see the module’s general specifications (GS 04L53B01-01EN).
*3 These values do not include the reference junction compensation accuracy.

Support measurement of up to 420 ch (actual input) by expanding channels across multiple units (multi-unit configuration)

Expand up to 420 ch by using the GX90EX expansion module. (GM10-2)
On the GM10-2 large capacity type, up to 1000 ch are available for recording when including MATH and communication channels. Connect units with LAN cables for dispersed installations.

Gm Image10

You connect directly with a LAN cable without connecting through a hub or repeater.
* You can also connect a GX60 expansion unit.

Reduce wiring with distributed installation

When the data logger is installed offsite (away from the DUT), you can place the sub unit at the site and monitor data without the need for long-distance wiring of thermocouples and other sensors.

Reduce wiring with distributed installation

Navigate with ease

Easy access from a Web browser

Through a Web browser you can monitor the GM in real time and change settings. You can easily build a seamless, low-cost remote monitoring system with no additional software.

Real time monitoring

With the scroll bar, you can seamlessly scroll between past and current trends.

Gm Image12

Enter settings online with a web browser

The setting screen lets you copy AI channel settings and other information to Excel for editing. You can reimport the data into the setting screen after editing.

Gm Image13

Trend, digital, and other real-time displays

Trend, digital, and other real-time displays

Dedicated software (free download) is available for loading waveforms and GM settings

Universal viewer

Data files saved on the GM can be viewed and printed. You can perform statistical computation over an area and export to ASCII, Excel, or other formats.

Gm Image15

Offline setting software

Save settings or transfer them to the GM. Connections can also be made easily via USB or Bluetooth.

Gm Image16

Safe to use in a wide range of temperatures

With operating temperatures of -20 °C to 60 °C, it supports a wide range of applications without concern about the installation environment.

Gm Image18

Monitoring and settings can also be done on a tablet

Supports Bluetooth (optional code /C8)

You can enter settings or monitor from a tablet without ever bringing a PC to the site. Dedicated applications is available for free download. For more information, visit our website.

Enables monitoring via Bluetooth

Bluetooth supports Android only.

Enables monitoring via Bluetooth

Enables monitoring via Wi-Fi

Wi-Fi supports both Android and iOS.

Powerful applications

Bluetooth connection

Simple to use for in-veheicle testing.

Bluetooth connection

USB connection

Service staff can easily perform maintenance on the GM.

USB connection

Data analysis made simple and mobile

High speed measurement (down to 1 ms)

Yokogawa's proprietary A/D converter allows the high speed module to measure data points as fast 1ms.

  • High speed (1 ms) measurement*
  • Proprietary A/D converter

* With 1ch per module. At 2 ms, 2 ch per module, and at 5 ms or more, all 4 ch per module.

GX90XA-04-H0 Analog input module (high speed AI)

Max. channels
Model Scan interval
1ms 5ms 10ms
GM10-1 1ch 5ch 10ch
GM10-2 5ch 25ch 32ch

Dual interval measurement with two different scan intervals

Users have the ability to choose two different scan intervals on a single GM system. This allows users the flexibility to measure various types of inputs with two different scan intervals in a single system. For example, this provides for efficient, simultaneous measurement of signals with slow fluctuations such as temperature, and fast-changing signals such as pressure and vibration. Modules can be assigned to measurement groups.

Dual interval measurement with two different scan intervals

PID control function

Control function

Enables PID and program control

  • PID control module
    2-loops per module, up to 20 loops per system
  • Setpoint program control function (/PG option)
    Up to 99 patterns

PID control function

Remote operation and monitoring

The web application enables remote operation and monitoring from a browser.

Remote operation and monitoring

MATH (including reports), and event actions

MATH function (/MT option)

Supports various kinds of math computation, including basic math and functions (square root, logarithms, trigonometry). Write formulas using variables for measured or computed data and save or display the results—this saves time and effort on post-processing. Create hourly, daily, monthly, and other reports with the Report function.

MATH function (/MT option)

Event actions

Ability to assign actions tied to specific events during the operation of the data acquisition station.

Event actions

Aerospace Heat Treatment Supports heat treatment application AMS2750/NADCAP

Calibration correction schedule control function (/AH option)

Schedule management for periodically executing calibration correction configuration and the like. You can set the input correction factor as a sensor correction factor and instrument correction factor. TUS software is available for easily creating TUS (temperature uniformity survey) reports.*

* For details on TUS software, consult with your Yokogawa dealer.

Input calibration is performed in the AI channel setting screen, and the calibration period settings are entered in the schedule management setting screen.

Record data in separate files per equipment set

Multi-batch Function (/BT option)

Record pre-defined channel groups to separate data files with independent start and stop control. You can create up to 12 batches.

Report creation and network functions (/MT option)

Report creation and network functions (/MT option)

Provides a variety of convenient networking functions

Modbus/TCP and Modbus/RTU Communications

GM supports Modbus TCP/IP client and server modes for Ethernet communications and Modbus/RTU master and slave modes for optional serial communications.

Modbus/TCP (Ethernet connection)

Using the Modbus/TCP and Modbus/RTU functions, you can display and save data from the server and slave devices on the GM.*

* Requires the communication channel (/MC option).

Modbus client/Modbus master

(You can connect up to 16 Modbus/TCP servers, or up to 32 servers with the GM10-2.)
(You can connect up to 31 Modbus/RTU slaves.)

Modbus/RTU (RS-422/485 connection)

Using the Modbus/TCP and Modbus/RTU functions, you can acquire GM data from upstream devices.

Modbus server/Modbus slave

EtherNet/IP Function (/E1 option)

GM supports EtherNet/IP server functions. You can access GM from PLCs or other devices and load measurement/MATH channels or write to communication input channels*(GM10-1: up to 300 ch, GM10-2: up to 500 ch).

* Requires the communication channel option (/MC option).

Gm Image26

CC-Link family SLMP communication (/E4 option)

Protocol function that enables connection from a GM to Mitsubishi Electric PLCs without sequencer programs. The GM can run as the SLMP client to write to a GM measured data PLC, or PLC data to communication channels*.

* Requires the communication channel option (/MC).

SLMP Communication (Mitsubishi PLC

Data acquisition on power measuring instruments (/E2 and /MC options)

Acquire precise digital data on the GM by digital communication connectivity to a power measuring instrument (WT series power analyzers) and record it along with the GM's measured data. Since it records a device's power consumption, temperature, and other phenomena at the same time, the GM is ideal for performance evaluation testing.

  • Models that can be connected:
    Yokogawa Meters & Instruments Corp.,
    WT1800/WT1800E (command type WT1800), WT500, WT300/WT300E (command mode WT300)
  • Max. no. of connections: 16

Gm Image22

OPC-UA Server (/E3 option)

Data acquired by the GM can be accessed through Ethernet communication from a host system (OPCUA client). Writing from upstream systems to GM communication channels requires the communication channel function (/MC option).

OPC-UA Server

Comes with communication functions that are compatible with the DARWIN data acquisition unit

The GM supports DARWIN communication commands. Use your current DARWIN communication programs as-is on the GM. It's easy to switch from an existing DARWIN unit.

* See your dealer or nearest Yokogawa representative for details.

Gm Image23

CENTUM/STARDOM communication package

  • CENTUM: LFS2432, DARWIN/DAQSTATION Communication package (for ALE111 [Ethernet])
  • STARDOM: NT365AJ DARWIN connection package

FTP-based file transfer

The FTP client/server functions allow you to easily share and manage data from a centralized file server

Gm Image25

E-mail messaging function

The GM can send a variety of informative e-mail messages that include alarm notification reports, periodic instantaneous data values, scheduled report data and other information.

Automatic network setup (DHCP) function

Using Dynamic Host Configuration Protocol (DHCP), the GM can automatically acquire the settings it needs (IP address) for network communications from a DHCP server. This makes i6t easier than ever to install the unit on a plant network.

Automatic network setup (DHCP) function

Time synchronization with network time servers

GM uses SNTP protocol in client mode to acquire time information from a network time-server. This function allows any number of GM units within a facility to have precisely synchronized time; all units will record data with coordinated date and time stamp information. In addition, GM can function as a server, providing time data to other SNTP client units on the network.

Time synchronization with network time servers

Rock-solid hardware and highly secure

Be confident that recorded data is saved

Supports long-duration and multichannel recording. Measured data is always stored to internal memory, and data is transferred to external storage media at regular intervals. Redundancy can be achieved by sending data to a server with the FTP client function. Securely saves measured data even in the event of a sudden power loss.

Gm Image28

Approximate sample time
Number of recording channels Total sample time
30 Approx. 71 days
100 Approx. 23 days
300 Approx. 7 days

With an internal memory of 1.2 GB and recording interval of 1 sec.

Select file formats according to your application

For increased security, measured data can be saved in binary format. This format is very difficult to decipher or modify in traditional text editors or other programs. To enable easy and direct opening of the data in text editors or spreadsheet programs, choose text format. This allows you to work with your measurement data without dedicated software.

ASCI data display
ASCII data display

Binary data display
Binary data display

Security enhancements

Safely sends and receives customer data.

Security enhancements

SSL: An encryption protocol for data sent over TCP/IP networks.

21 CFR Part 11 support (/AS option)

With the advanced security function option, GM supports the USA FDA's Title 21 CFR Part 11 regulations (for the pharmaceutical manufacturing industry). It gives you access to a login function for requiring user names, IDs, and passwords, plus electronic signatures, audit trails, an anti-tampering function, an Active Directory-based password management function, and other security features.

21 CFR Part 11 support (/AS option)

Key lock

You can use settings to lock the GM10 operation keys in order to avoid accidental start/stop of measurement or computation.

Key lock

Analog front end module

A proprietary A/D converter delivers high speed, high precision data acquisition. (High-speed AI, PID Control module)

Analog front end module

Standards supported

Standards supported

Analog input module

GX90XA

Specifications

Model GX90XA
Input type
(Inputs: 10)
DC voltage*1, standardized signal*1, thermocouple*1, RTD*2, DI*1, DC current (with external shunt resistor)*1, DC current*3, resistance*4
DCV 20 mV, 60 mV, 200 mV, 1 V, 2 V, 6 V, 20 V, 50 V, 100 V*5
Standard signal 0.4-2 V, 1-5 V
Resistance 20, 200, 2000 Ω
Thermocouple R, S, B, K, E, J, T, N, W, L, U, W97Re3-W75Re25, KpvsAu7Fe, Platinel 2, PR20-40, NiNiMo, W/WRe26, N(AWG14), XK GOST
RTD Pt100, JPt100, Cu10 GE, Cu10 L&N, Cu10 WEED, Cu10 BAILEY, Cu10 (20°C) α=0.00392, Cu10 (20°C) α=0.00393, Cu25 (0°C) α=0.00425, Cu53 (0°C) α=0.00426035, Cu100 (0°C) α=0.00425, J263B, Ni100 (SAMA), Ni100 (DIN), Ni120, Pt25, Pt50, Pt200 WEED, Cu10 GOST, Cu50 GOST, Cu100 GOST, Pt46 GOST, Pt100 GOST, PT500*4, PT1000*4
DI Level, Contact
DC current 0-20 mA, 4-20 mA
Scan intervals

1/2/5/10/20/50/100/200/500ms, 1/2/5s

Scan interval by type

Suffix code Scan interval
1ms 2ms 5ms 10ms 20ms 50ms 100ms 200ms 500ms 1s 2s 5s
-U2
-C1
-L1
-T1
-H0
-R1
Power supply and consumption Supplied from main unit, power consumption: 2 W or less
Insulation resistance Between input circuits and internal circuitry: 20 MΩ or greater (at 500 V DC)
Withstand voltage Between the input circuits and the internal circuitry: 3000 VAC for one minute (current input type and low withstand voltage type: 1500 VAC for one minute)
Between analog input channels: 1000 V AC for one minute (excluding b terminals for universal input type) (low withstand voltage type: 400 VAC for one minute, high speed universal type: 3000 V AC for one minute)
Terminal types M3 screw terminals or clamp terminals
Weight Approx. 0.3 kg

*1 Cannot be set for the current input type (type suffix code: -C1) or 4-wire RTD/resistance type (type suffix code: -R1).

*2 Cannot be set for the current input type (type suffix code: -C1), electromagnetic relay type (type suffix code: -T1), or low withstand voltage type (type suffix code: -L1).

*3 Can only be set with current input type (type suffix code: -C1).

*4 Can only be set with 4-wire RTD/resistance type (type suffix code: -R1).

*5 Can only be set with high speed universal type (type suffix code: -H0).

Model and Suffix Codes

Model Suffix Code Description
GX90XA           Analog input module
Number of channels -04         4 channels (-H0 type only)
-06         6 channels (-R1 type only)
-10         10 channels
Type -C1       Current, scanner type (isolated between channels)
-L1       Low withstand voltage DCV/TC/DI, scanner type (isolated between channels)
-U2       Universal, Solid state relay scanner type (3-wire RTD b-terminal common)
-T1       DCV/TC/DI, Electromagnetic relay scanner type (isolated between channels)
-H0       High speed universal, individual A/D type (isolated between channels)
-R1       4-wire RTD/resistance, scanner type (isolated between channels)
- N     Always N
Terminal form -3   Screw terminal (M3)
-C   Clamp terminal
Area N General

Analog output module

Specifications

Model GX90YA
Output type (outputs: 4) Transmission output, manual output
Range 4–20 mA or 0–20 mA
Output update interval 100 msec (shortest)
Load resistance 600 Ω or less
Resolution 0.002%
Power supply and consumption Supplied from main unit, power consumption: 3W or less
Insulation resistance Between output circuits and internal circuitry: 20 MΩ (at 500 VDC)
Between output channel terminals: 500 VDC, 20 MΩ or greater
Withstand voltage Between output circuits and internal circuitry: 1500 AC for one minute
Between output circuits: 500 VAC for one minute
Terminal type M3 screw terminals or clamp terminals
Weight Approximately 0.2 kg

Model and Suffix Codes

Model Suffix Code Description
GX90YA           Analog output module
Number of channels -04         4 channels
Type -C1       Current output (isolated between channels)
- N     Always N
Terminal form -3   Screw terminal (M3)
-C   Clamped terminals
Area N General

Digital input module

GX90XD

Specifications

Model GX90XD
Input types
(Inputs: 16)
  DI or pulse input*1 (Open collector or non-voltage contact)
ON/OFF detection Open collector: Voltage of 0.5 V DC or less when ON, leakage current of 0.5 mA or less when OFF
Non-voltage contact: Resistance of 200 Ω or less when ON, 50 kΩ when OFF
Contact rating 12 V DC, 20 mA or more
Power supply and consumption Supplied from main unit, power consumption: 0.7 W or less
Insulation resistance Between input terminals and internal circuitry: 20 MΩ or greater (at 500 V DC)
Withstand voltage Between input terminals and internal circuitry: 1500 V AC for one minute
Terminal types M3 screw terminals or clamp terminals
Weight Approx. 0.3 kg

Pulse input specifications*1

Counting system The rising edge of the pulse is counted.
Max. pulse period 250Hz (The chattering filter : OFF)
125Hz (The chattering filter : ON)
Minimum detection pulse width Low (close), High (open), both is 2 ms or more
Pulse detection period 1ms
Pulse measurement accuracy ± 1 pulse
Pulse count interval Measurement interval

Filter

The chattering filter can be switched On/Off. (When the chattering filter is off, connect GX/GP so that it is not affected by the noise.)

*1 Integration requires the math function (optional code /MT).

Model and Suffix Codes

Model Suffix Code Description
GX90XD           Digital input module
Number of channels -16         16 channels
Type -11       Open collector/Non-voltage, contact (shared common), Rated 5 VDC
- N     Always N
Terminal form -3   Screw terminal (M3)
-C   Clamp terminal
Area N General

Digital output module

GX90YD

Specifications

Model GX90YD
Output types (outputs: 6) Relay contact (c contact)
Rated load voltage 100 to 240 V AC or 5 to 24 V DC
Max. load voltage/current 264 VAC or 26.4 VDC, 3A/point (resistance load)
Power supply and consumption Supplied from main unit, power consumption: 1.4 W or less
Insulation resistance Between output terminals and internal circuitry: 20 MΩ (at 500 VDC)
Withstand voltage Between output terminals and internal circuitry: 3000 V AC for one minute
Terminal types M3 screw terminals
Weight Approx. 0.3 kg

Model and Suffix Codes

Model Suffix Code Description
GX90YD           Digital output module
Number of channels -06         6 channels
Type -11       Relay, SPDT(NO-C-NC)
- N     Always N
Terminal form -3   Screw terminal (M3)
Area N General

Expansion module

GX90EX

Model and Suffix Codes

Model Suffix Code Description
GX90EX          I/O expansion module
Port -02       2 Ports
Type -TP1     Twisted pair cable
- N   Always N
Area -N Standard accessories

Digital input/output module

GX90WD

Specifications

Model  GX90WD
Input types
(Inputs: 8)
  DI or pulse input*1 (Open collector or non-voltage contact)
ON/OFF detection Open collector : Voltage of 0.5 V DC or less when ON, leakage current of 0.5 mA or less when OFF
Non-voltage contact : Resistance of 200 Ω or less when ON, 50 kΩ when OFF
Contact input rating 12 VDC, 20 mA or more
Output type (outputs: 6)   Relay contact (C contact)
Rated load voltage When connected to the main circuit (fi rst-order power supply), 150 VAC or less
When connected to a circuit derived from the main circuit (second-order power supply), 250 VAC or less (the main circuit is 300 VAC or less and uses an isolated transformer) or 30 VDC or less
Max. load current 2 A (DC)/2 A (AC), resistive load
Power consumption 1.9 W or less
Insulation resistance Between input terminals and internal circuitry: 20 MΩ or greater (at 500 VDC)
Between output terminals and internal circuitry: 20 MΩ or greater (at 500 VDC)
Withstand voltage Between input terminals and internal circuitry: 1500 VAC for one minute
Between output terminals and internal circuitry: 3000 VAC for one minute
Terminal types M3 screw terminals
Weight Approx. 0.3 kg

Each unit (GX/GP main unit and expandable I/O), can use 1 module only.

Pulse input specifications*1

Counting system The rising edge of the pulse is counted.
Max. pulse period 250Hz (The chattering filter : OFF)
125Hz (The chattering filter : ON)
Minimum detection pulse width Low (close), High (open), both is 2 ms or more
Pulse detection period 1ms
Pulse measurement accuracy ± 1 pulse
Pulse count interval Measurement interval

Filter

The chattering filter can be switched On/Off. (When the chattering filter is off, connect GX/GP so that it is not affected by the noise.)

*1 Integration requires the math function (optional code /MT).

Model and Suffix Codes

Model Suffix Code Description
GX90WD           Digital input/output module
Number of channels -0806         8 channel DIs, 6 channel DOs
Type -01       Open collector/non-voltage contact (shared common), rated 5 VDC; Relay, SPDT, (NO-C-NC)
- N     Always N
Terminal form -3   Screw terminal (M3)
Area N General

Pulse input module

Specifications

Model GX90XP
Number of inputs 10
Measurement interval 100 ms (shortest)
Input type Contact (open collector, voltage-free contact), level (5 V logic)
Input range Up to 20 kHz*
* 30 Hz when the chattering filter is in use (On)
Minimum detection pulse width 25 μs*
* 15 ms when the chattering filter is in use (On)
Measurement accuracy Count ± 1 pulse
During integration, the following accuracies are added.
Upon MATH start: +1 measuring period
Upon MATH stop: -1 measuring period
* Integration requires the math function (optional code /MT).
Chattering filter Removes chattering up to 5 ms (can be turned on/off on each channel)
Hysteresis width Approx. 0.2 V
Contact, transistor rating Contact: 15 V DC or higher and 30 mA or higher rating.
Minimum applicable load current 1 mA or less.
Transistor: With the following ratings: Vce > 15 VDC, Ic > 30 mA
Maximum input voltage ±10 V DC
Insulation resistance Between input terminals and internal circuitry:
20 MΩ or greater at 500 V DC
Withstand voltage Between input terminals and internal circuitry: 1500 V AC for 1 minute

 

Model and Suffix Codes

Model Suffix code Description
GX90XP           Pulse input module
Number of channels -10         10 channels
Type -11       DC voltage/open collector/non-voltage contact (shared common), rated 5 VDC
N     Always N
Terminal form -3   Screw terminal (M3)
-C   Clamp terminal
Area N General

PID control module

Specifications

Model GX90UT
Control loops Number of loops 2
Analog input (measured input) Measured points 2
Measurement type DC voltage (DCV)/standardized signal, TC/RTD, DI (LEVEL and non-voltage contact)/DC current (with external shunt resistance)
Scan (control) interval 100 ms or 200 ms (system global setting)
Analog output (control output/transmission output/sensor power supply) Outputs 2
Output type Power supply for current, voltage pulse, or sensors.
Current output: 4-20 mA or 0-20 mA
Voltage pulse output: ON voltage = 12 VDC or more (load resistance 600 Ω or more), OFF voltage = 0.1 VDC or less
Can be used as a sensor power supply (13.0-18.3 VDC)
Digital input (switching the SP, operation mode, etc.) Inputs 8
Input format Non-voltage contact and open collector
Contact rating: 12 VDC or more, 20 mA or more
Digital output (of alarms, events, etc.) Outputs 8
Output format Open collector (sink type)
Output contact capacity Max 24 VDC, 50 mA
Withstand voltage/insulation resistance See PID control module general specifications (GS 04L51B01-31EN)
Terminal type M3 screw terminals
Weight Approximately 0.3kg

Model and Suffix Codes

Model Suffix Code Description
GX90UT           PID control module
Number of loops -02         2 loops
Type -11       8 DIs, 8 DOs
N     Always N
Terminal form -3   Screw terminals (M3)
Area N General

as of March, 2017

The SD cards of the following manufacturers have been verified for use with SMARTDAC+® GX/GP/GM, µR10000™/µR20000™ and FX1000™. However, please note that Yokogawa does not guarantee normal operation of the SD card when using with products listed below.

SMARTDAC+ GX
Applicable Models: GX10, GX20, GX20W
SMARTDAC+ GP
Applicable Models: GP10, GP20
SMARTDAC+ GM
Applicable Models: GM10

√: Verified
Manufacturer Capacity Manufacturer Model GX10 GX20 GP10 GP20 GX20W GM10
SanDisk 16GB SDSDXS-016G  
SanDisk   8GB SDSDXS-008G  
SanDisk 32GB SDSDXVE-032G
SanDisk 32GB SDSDXS-032G
SanDisk 32GB SDSDXL-032G
SanDisk 16GB SDSDXL-016G
SanDisk   8GB SDSDXL-008G

Applicable Models: µR10000/EM1, µR20000/EM1 

√: Verified
Manufacturer Capacity Manufacturer Model µR10000/EM1 µR20000/EM1
SanDisk 32GB SDSDXVE-032G
SanDisk 32GB SDSDXS-032G

Applicable Models: FX1000

√: Verified
Manufacturer Capacity Manufacturer Model FX1000
SanDisk 32GB SDSDXVE-032G
SanDisk 32GB SDSDXS-032G

In rare cases, the SD card is not recognized or generates an error when inserted into the instrument. If this occurrs, try the following.

  • Eject the SD card, then reinsert it.
  • Replace with a SD card that you know to be working normally.
  • Format the SD card on the Products (all data on the card will be deleted).

Please direct inquiries regarding the other manufacturers' verified SD cards above to their manufacturers.
Please note that sales of the above-mentioned SD card may be discontinued from the manufacturer without prior notice.

 

Overview:

Improving manufacturing efficiency demands constant action - from uncovering operational waste to identifying areas for continuous improvement. Namely, we must always pursue a cycle of visualizing, analyzing, and solving energy saving challenges.

Overview:

The DTSX is a reliable and robust tool for fire detection over long distances and large areas, such as tunnels.

Brochures
Instruction Manuals
General Specifications
Software
Technical Information
Certificates
Drawings

Product Overviews

    Overview:

    Smart user interface, smart architecture, and smart functionality is achieved in the Yokogawa SMARTDAC+ data acquisition and control product series. SMARTDAC+ consists of the GX and GP touch screen data acquisition stations and the most recent addition – the GM data acquisition and data logging system which is both compact and modular.

Looking for more information on our people, technology and solutions?


Contact Us
Top