Integration of Real-time Utility Monitoring with a DCS

下载 (912 KB)

Introduction

Photo 1

The discharge of improperly treated industrial chemicals and fuel gas can have a major impact on the environment, posing a serious threat to public health. Concurrent with the global growth of manufacturing operations to keep pace with market trends, many countries are taking measures to deal with environmental problems. In Japan, for instance, the Air Pollution Control Law and the Water Pollution Control Law require businesses to control toxic emissions. Both are revised periodically. To comply with government regulations and fulfill their responsibilities to society, businesses are upgrading their monitoring and control of waste treatment utilities, including waste water treatment and dust filtering facilities.

Effluent control in Japan

Closed bodies of water such as lakes, inland seas, and bays where there is relatively little inflow or outflow are particularly vulnerable to water pollution. Eutrophication caused by organic pollution can lead to problems such as massive plankton outbreaks and red tides. With the implementation in 2001 of the fifth stage of the Japanese Total Pollutant Load Control Program, chemical oxygen demand (COD) restrictions were enhanced. In addition, nitrogen and phosphorus were added to the list of controlled substances as they are believed to be a cause of red tides.

Air pollution control in Japan

Respiratory function can be affected by suspended particulate matter. Volatile organic compounds (VOC), which were once widely used as cleaning agents in the manufacturing of semiconductors and other electric and electronic devices, are thought to play a role in generating photochemical oxidants. The Japanese government placed restrictions on VOC in 2004 when it revised the Air Pollution Control Law.

 

Expected Benefits

Industrial Effluents

The waste treatment facilities and main plants integration, achieved with the new "Integrated Operation" system architecture, contributes toward the reduction of factory related pollution with following benefits:

Blind spots eliminated

When utility data is displayed on multiple instruments and/or recorders, blind spots can occur in utility monitoring. By bringing together this utility data in the STARDOM FCN/FCJ hybrid PLCs, this data together with other plant status information can be monitored and manipulated from the DCS HMI. This eliminates blind spots.

Reduced risk of uncontrolled discharge of industrial effluents

From the central control room, which is manned around the clock, personnel operate and control the whole plant from the Distributed Control System (DCS) Human Machine Interface (HMI). By integrating into the DCS HMI the data and alarms from utilities, which are often monitored independently, the probability of an uncontrolled discharge of industrial effluents into a river is dramatically reduced. This also makes it possible to reduce the frequency of on-site patrols.

Agile action to the frequent utility revamps

In a new plant, the utility data can be integrated in the DCS HMI. Whenever utilities are revamped, the hybrid PLC logic needs to be modified. Although these changes can affect the operation of the DCS controllers, which handle the main process, no changes are made to the DCS logic. Modifying the DCS logic is not the solution to this problem. With an integrated operation architecture, the DCS logic does not need to be modified. The hybrid PLC data that has been modified as a result of the utility revamps can be accessed by the DCS via the System Integration OPC Station (SIOS). This enables the hybrid PLC data to be handled in the same way as the data from the DCS function blocks.

Reduced capital expenditure (CAPEX) for utility revamps

Each time utilities are revamped, rewiring and re-engineering of the DCS controllers is required. This new architecture eliminates the need to rewire the DCS controller and modify its logic, reducing the overall cost of a utility revamp. This is made possible by the SIOS, which allows the hybrid PLC function ownership due to longer sensor prove life-time.

Reduced training time

Every time a new system is installed, personnel must undergo training to learn how to operate it. With the integrated operation architecture, this is not necessary because there is no change in how the data and alarms from the FCN/JCJ hybrid PLCs are handled from the DCS HMI. Also, the automatically generated FCN/FCJ tuning windows have the same look and feel as the DCS tuning windows.

 

Process Description

Monitoring and Control Systems for Waste Treatment Utility

Monitoring and control systems for waste treatment utility

For waste treatment facilities to comply with stricter regulations and operate safely and efficiently, monitoring and control systems with the following characteristics are required:

  • Can flexibly accommodate regulatory changes in monitoring subjects and limit values
  • Monitoring and control points can be easily added at each process step
  • The monitoring and control system can cope in real time with emergencies such as the discharge of toxic effluents into a river in a remote location.
  • Seamlessly integrates with a centralized monitoring and control system, enabling integration of utility and production processes
  • Can operate with high reliability and stability for long periods of time
 

Challenge of Conventional Monitoring and Control Systems

Existing waste treatment utilities employ the following systems, depending on the facility scale and the treatment complexity.

On-site monitoring

Operation and monitoring with on-site instruments

Instruments are installed on-site. Single-loop controllers and the like perform control as well as operation and monitoring functions, and data are stored on recorders. This system is employed with utilities located in remote locations, and requires regular site patrols.

  • Relying chiefly on periodic on-site patrols does not allow real-time responses to emergency alarms.
  • The inability to operate in real time makes it difficult to control the utility if the emergency level is raised.
  • Readings are displayed on multiple instruments or panels, making oversights more likely.
  • Data displayed on different panels cannot be integrated at a central location.

Control through PLC and operation and monitoring with on-site displays

The system is located far from the main plant and thus performs control and monitoring independently. On-site personnel or periodic patrols are available.

  • When unattended, the system cannot respond to emergency alarms in real time.
  • When there are multiple utilities, their statuses cannot be centrally controlled.
  • Integrated management of the main and utility processes is not possible.

Centralized monitoring

Control through PLC and operation and monitoring on a DCS via data integration using Modbus or other method

Control is localized within the utility and only important data are collected and monitored from the centralized monitoring and control system.

  • To comply with stricter regulations and accommodate data from an increased number of monitoring points, the DCS controller logic needs to be modified.

Control, monitoring, and operation all performed on a DCS using remote I/O

Measurements for all monitoring points are input to the DCS. As both monitoring and control are performed the centralized system, the operator can make real-time responses to changes in the utility status.

  • Changes to monitoring points and the utility's control logic require modification of the DCS logic.
  • Control of both main and utility processes requires more complex DCS logic.
  • The utility logic places a heavy demand on DCS resources CPU and I/O points.
 

Solution

System ConfigurationThe Yokogawa solution: Integrated operation

Same look and feel operation and monitoring on the DCS HMI

To overcome the limitations of conventional utility systems, Yokogawa proposes a new utility monitoring and control system architecture that seamlessly integrates hybrid PLCs with the DCS. The new system architecture can flexibly accommodate changes made to improve the operational efficiency of utilities.

Via a system integration OPC station (SIOS), the function blocks of the hybrid PLCs (FCN/FCJ controllers) can be operated and monitored from the DCS human-machine interface (HMI), and the display of data from both systems has the same look and feel. And with the Consolidated Alarm Management System for HIS (CAMS for HIS), all alarm management is integrated. Both the data and the alarms from the FCN/FCJ are integrated into the DCS HMI.

No change to the DCS system architecture

The monitoring and control of utilities by the FCN/FCJ controllers can be integrated into the DCS without having to change the DCS system logic or architecture. This is because the data from the FCN/FCJ hybrid PLCs passes through the SIOS, enabling it to be handled in the same way as the data from the DCS function blocks.

Automatic creation of tuning windows

Tuning windows for the hybrid PLC function blocks are automatically created in the DCS HMI. Specially adapted tuning windows for these function blocks are not required. 

Conclusion

There is an increasing need for a DCS with the ultra-high reliability required by plants. At the same time, the ability to raise productivity by flexibly improving and expanding subsidiary facilities and utilities is required. Distributing the facility and utility monitoring and control logic among the hybrid PLCs facilitates plant expansion and improvement, but with a conventional distributed system the DCS logic must be modified.

Yokogawa proposes SIOS-based integrated operation for the same look & feel display of hybrid PLC function blocks on the DCS HMI. The ability to access the hybrid PLC function blocks in the DCS HMI makes possible the automatic generation of tuning windows and trend windows, substantially improving engineering efficiency. Through the seamless integration of independent utilities in a centralized monitoring and control system, an entire plant can be monitored and operated in real time from the DCS HMI, increasing the utilities' efficiency and operational safety.

行业

  • 制药

    能否充分利用大型新兴市场的机遇,是目前制药行业面临的重大挑战。现在制药公司比以往任何时候都更需要引入精益化生产技术,以提高盈利能力。作为全球知名工业自动化供应商,横河电机致力于为客户的优化生产实践提供卓越的解决方案。

    更多
  • 化工

    化工厂依靠连续和批量的生产过程,每个生产过程对控制系统都有不同的要求。连续的过程需要一个强大而稳定的控制系统,该系统不能因为自身失效而导致生产线关闭;批量过程的重点在于拥有一个可以灵活调整公式程序的控制系统。两种系统都需要在产品质量记录中进行管理,并且能够执行非常规操作。横河电机凭借广泛的产品组合、经验丰富的系统工程师、遍及全球的销售和服务网络,为每个工厂流程提供解决方案。

    更多
  • 水和废水

    横河电机通过开发更节能的技术,帮助减少运营的碳排放,以及构建保护环境免受污染的坚固建筑,为可持续水生产提供控制解决方案。横河凭借先进的技术和广泛的应用专业知识与客户合作,提供可持续水生产的解决方案,促进客户的业务,并让整个工厂在生命周期中增加价值。横河的技术和产品可提高工厂的性能,确保它们在当今的水处理领域中具有竞争力,并降低运营成本。横河支持市政和工业水处理领域的各种水控制方面的应用。

    更多
  • 水处理

    横河电机提供理想的解决方案,以改善水处理厂的运行,使其更加可靠。这些解决方案包括复杂的技术、过硬的产品质量和贯穿生命周期的广泛应用技巧。

    更多
  • 污水处理

    污水处理厂使用大量的电动机、泵、鼓风机等,因此降低其耗电量以降低运营成本是十分重要的。横河电机提供控制解决方案,以提高能源效率。

    更多
  • 火电

    使用煤、石油或天然气作为燃料的火力发电占全世界发电量的大部分。

    更多
  • 特种和精细化工

    横河电机长期以来一直为特种和精细化工的客户提供服务。我们拥有可为您提供卓越可靠性和灵活性的批量解决方案,同时我们还有在设计批量解决方案时可应对各种复杂要求的行业专家。我们承诺与横河电机的合作伙伴关系期间,确保您能够在保证安全和遵从法规的前提下,生产满足客户需求的产品。

    更多
  • 造纸

    面对不断变化的市场需求,造纸行业的竞争也愈演愈烈。横河电机可以帮助节能工厂实现全球可持续性发展。

    更多
  • 采矿和金属

    采矿作业是从地球上生产出有价值的矿产或地质材料。经济成本的回收通常需要高产量和高可用性的流程,保持低成本运营,严格保证安全性并遵守环保法规。

    更多
  • 钢铁

    在钢铁工业中,不仅要提高产品质量,而且要提高制造和运营技术,解决环境问题、提高能源效率。横河帮助客户创造理想的工厂,并与客户共同成长。

    更多
  • 食品和饮料

    在横河电机,我们了解当今的食品和饮料公司在气候变化、消费者需求和全球竞争力增强方面面临着前所未有的挑战。克服这些挑战需要创新的解决方案,需要重点关注生产、资产管理以及食品安全和质量等关键领域。

    更多

相关产品&解决方案

  • 集散控制系统(DCS)

    横河电机的集散控制系统(DCS) 可实现工业过程的自动化和控制,并提高业务绩效。30,000多套系统的经营者选择采用横河电机的DCS来实现其生产目标。

    更多

置顶
WeChat QR Code
横河电机(中国)有限公司