Introduction
Control of sodium chloride (NaCl) concentration at a salt dissolver where solid salt is dissolved in water, is highly important because of the electrolysis efficiency. A conventional way of measuring the concentration of supersaturated NaCl solution had been performed by using non-contact type sensors (e.g., γ-ray density meter) since NaCl, impurities, and precipitates are in the solution. In this way, there were disadvantages such as troublesome maintenance and therefore, the radiation control is required for γ-ray density meter. Responding to these backgrounds, the FLXA202 2-wire inductive conductivity analyzer provides concentration reading and realizes to improve substantial maintainability, cost performance and measurement accuracy.
Caustic Soda Production Process
Expected Benefits
- Measures NaCl concentration in salt dissolvers
- Reduces operating costs
Process Overview
In an electrolysis plant, the solid salt is dissolved in water in a salt dissolver to make brine. This brine contains impurities, such as calcium, magnesium or sulfates, that decrease electrolysis efficiency. The brine is purified by removing these impurities before being fed to an electrolyzer, where the purified brine is electrolyzed to produce caustic soda and chlorine. The caustic soda solution produced at the cathode in the electrolyzer is concentrated in a multiple effect evaporator, as a result the concentration is increased from approximately 32% to 48%.
Solution Details
Measurement system
2-wire inductive conductivity system
Sensor | ISC40G(J)-GG-T1-☐☐ |
---|---|
Flow-through holder | ISC40FF(J)-PJ |
Transmitter | FLXA202-D-BーD-☐-C5-NN-A-N-LA-☐-NN |
Inductive Conductivity Sensor & Transmitter Installation Diagram
Utilities
FLXA202 2-wire inductive conductivity analyzer | |
---|---|
Power supply voltage: | 17 - 40 V DC (from distributor) |
Power consumption: | 0.9 VA maximum |
PH201G distributor | |
Power supply: | |
100 V: | 20 to130 V DC/80 to 138 V AC, 47 to 63 Hz |
220 V: | 120 to 340 V DC/138 to 264 V AC, 47 to 63 Hz |
Power consumption: | 24 V DC: approx. 200 mA |
100 V AC: approx. 7 VA | |
220 V AC: approx. 11 VA |
Notes
Sampling should be done in the supernatant liquid in a salt dissolver. The supernatant liquid is collected in a settling tank and then the supernatant liquid of the tank is transported to a measurement tank where the sensor is installed.
Field Data
1. Process conditions (salt dissolver)
Temperature: | Approx. 65°C |
---|---|
Pressure: | Atmospheric pressure |
Sample: | Supersaturated brine |
NaCl concentration control range: | 200 to 360 g/L |
--> 18.1 to 30 wt%* |
* Depends on user's actual data of specific gravity.
2. FLXA202 setting parameters
Relationship between conductivity and concentration is based
on the linear approximation of S = 16.3x that is obtained by actual measurement using SC72 Personal Conductivity Meter.
- NaCl temperature compensation table is used
- Reference temperature setting: 25°C
Concentration (%) | Conductivity (mS/cm) |
---|---|
18 | 293 |
24 | 391 |
30 | 489 |
行业
-
化工
化工厂依靠连续和批量的生产过程,每个生产过程对控制系统都有不同的要求。连续的过程需要一个强大而稳定的控制系统,该系统不能因为自身失效而导致生产线关闭;批量过程的要点在于拥有一个可以灵活调整地公式和程序的控制系统。两种系统都需要在产品质量记录中进行管理,并且能够执行非常规操作。横河电机凭借广泛的产品组合、经验丰富的系统工程师、广泛的销售和服务网络,为工厂流程提供解决方案。
-
特种和精细化工
横河电机长期以来一直为特种和精细化工的客户提供服务。我们拥有可为您提供可靠性和灵活性的批量解决方案,同时我们还有在设计批量解决方案时可应对各种复杂要求的行业专家。我们承诺在您与横河电机的合作伙伴关系期间,确保您能够在保证安全和遵从法规的前提下,生产满足客户需求的产品。
相关产品&解决方案
-
2-Wire Transmitter/Analyzer FLXA202
The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.
-
FLXA202/21两线制变送器/分析仪
FLEXA™系列分析仪用于工业设施中的连续在线测量。它是灵活的两线制分析仪,可选择单传感器或双传感器测量。
-
ISC40电感式(环形、无电极)电导率传感器
ISC40型传感器与EXA ISC分析仪组合使用。在可靠性、准确性、可调性和性价比方面,该组合满足甚至优于对电导率测量的期望。
-
pH和ORP分析仪
pH和ORP流量计、分析仪和变送器用于pH和ORP的连续过程监测,以确保水/产品质量,如监测污水排放、批量中和、浆料存储、洗涤塔,冷却塔、化学品、水/废水处理和许多其他应用。
-
电导率传感器
电导率传感器和电极用于测量过程电导率、电阻率、WIFI、软化水、RO水、百分比浓度、锅炉水排污和TDS。有伸缩式、流通式、浸入式和直插式等多种安装选项。选择合适的电极/传感器对优化测量结果至关重要。