Introduction
Wastewater from electroplating facilities and certain types of chemical plants contains toxic forms of hexavalent chromium such as chromate and dichromate. The hexavalent chromium in this wastewater must be reduced before the water can be discharged. This requires a two-step process: hexavalent chromium (CR6) is reduced to trivalent chromium (CR3); and CR3 is precipitated as chromium hydroxide. As the oxidation reduction potential (ORP) and the speed of the reduction reaction are closely tied to the pH value, ORP and pH analyzers are used to ensure proper control of the reduction process through such means as the injection of reducing agents.
pH and ORP measurements in these reaction tanks are complicated by the presence of chrome and sulfur dioxide, which can poison the sensor reference under certain circumstances. pH and ORP control in these applications may be conducted using alarm relays and a simple on/off control scheme such as available in the FLXA402 Analyzer. Alternatively, the 4-20mA current output can be used directly for proportional control, or sent to a distributed control system as needed. The FLXA21/FLXA202/FLXA402 can measure both ORP and pH. Both 2-wire and 4-wire analyzers are suitable for this measurement system. A gold electrode should be used for ORP measurement of chromium wastewater.
Reducing trivalent chromium process
Expected Benefits
- Measures pH/ORP of chromate wastewater continuously
- Reduces operating costs
Process Overview
First, hexavalent chromium, either in the form of chromate or dichromate, is reduced to trivalent chromium. Wastewater flows into the first reaction tank, where the pH is measured and sulfuric acid is automatically brought into the process until a pH set point value in the acidic range is achieved. The reaction time is just a few minutes, and a lower pH for an even faster reaction would require considerably more acid. At the same time, the oxidation reduction potential (ORP) of the solution is measured, and sulfur dioxide (SO2), sodium sulfite, or sodium metabisulfite is automatically injected until an ORP value of approximately 280 mV is achieved.
Then in the second tank, the pH is raised to 8.5 by the addition of an alkaline solution such as ammonia or caustic (NaOH), where it is converted to chromium hydroxide. The precipitate, although heavier than the water, does not drop to the bottom due to agitation in the tank. The mixed slurry flows to a settling tank, where the trivalent (Cr3+) chrome settles to the bottom and the clear chromium-free water flows over the tank for further treatment. Chemicals known as coagulants are sometimes added to the second reaction tank to help form larger particles and aid in sludge removal. The reducing agent may be a substance such as ferrous sulfate, sodium metabisulfite, or sulfur dioxide. Chemicals known as coagulants are sometimes added to the second reaction tank to help form larger particles and aid in sludge removal.
Solution Details
Measurement system
2-wire/4-wire pH/ORP measurement system
Sensor/Holder | |
---|---|
KCl refillable ORP sensor: | OR8EFG-AU-☐☐-TT1-☐*A |
KCl refillable pH sensor: | PH8EFP-☐☐-TN-TT1-N-☐*A |
Submersion type holder: | PH8HS-PP-☐☐-T-NN-NN*A |
Terminal box (when needed) | |
WTB10-PH1 | (for 2-wire system) |
WTB10-PH3 | (for 4-wire system) |
Converter/transmitter: | |
2-wire pH/ORP transmitter (pH+ORP 2 input): | FLXA21-D-P-S-☐☐-P1-P1-A-N-LA-N |
Distributor (for 2-wire system): | |
PH201G- A☐*C | |
4-Wire Converter (pH+ORP 2 input): | FLXA402-A-B-□□-P1-P1-□□-NR-N-N-N-NN |
- Check solutions for ORP analyzer
Oxidation-reduction potential of check solutions (quinhydrone/iron solutions)
A check solution is used to determine whether the ORP sensor is operating correctly. There are two types of check solutions: quinhydrone and iron.
Quinhydrone solution: approx. 200 to 300 mV
Iron solution: approx. 420 to 520 mV
Unlike a pH standard solution, an ORP check solution does not always indicate a constant reference value. Whether the sensor is operating normally can be determined by seeing whether its readings are within the acceptable range.
Preparation of a check solution (250 mL)
Quinhydrone solution: Dissolve the following reagent in pure water and dilute to 250 mL.
Quinhydrone salts: P/N K9024EC
Ferrous & ferric: dissolve the following reagent in a 2-mol/L sulfuric acid solution and dilute to 250 mL.
Ferrous & ferric salts: P/N K9024ED - Use of a gold electrode for ORP measurement
For ORP measurement of chromate wastewater, the use of a gold electrode is recommended.
Utilities
- FLXA21/FLXA202
Power supply: 23 to 40 V DC (from distributor) - PH201G distributor (for 2-wire system)
Power supply:
100 V: 20 to130 V DC/80 to 138 V AC, 47 to 63 Hz
220 V: 120 to 340 V DC/138 to 264 V AC, 47 to 63 Hz
Power consumption:
24 V DC: approx. 200 mA
100 V AC: approx. 7 VA
220 V AC: approx. 11 VA - FLXA402
Power supply: 90 to 264 V AC, 50/60 Hz
Power consumption: approx. 35 VA
產業別
-
Water & Wastewater
促進永續水循環是永續發展目標(SDG)之一。 橫河電機一直致力於提供先進的數位控制解決方案,以穩定供應清潔安全的水、保護水環境的廢水處理、水損耗管理以及優化工廠運作減少二氧化碳排放和運行成本。 利用我們領先的技術、可靠的產品以及在世界各地不同供水項目中豐富的專業知識和經驗,我們與客戶合作提供可持續的水務解決方案,以促進客戶的業務並在整個工廠生命週期中增加價值。
橫河電機支援公用和工業用水的各種供水控制應用。
相關產品&解決方案
-
FU20/FU24/PH20一體化pH/ORP (REDOX)傳感器
PH20/FU20/FU24一體化pH/ORP傳感器體現了橫河電機如何將“簡單即好”這句格言應用於傳感器技術。
-
兩線式Dual Channel分析儀 FLXA21
FLEXA™ 系列分析儀用於工業裝定的連續線上測量,具有單感測器或雙感測器測量選項,是目前最靈活的兩線式分析儀。
-
兩線式液體分析計FLXA202
FLEXA™ 系列分析儀用於工業裝定的連續線上測量,具有單感測器或雙感測器測量選項,是目前最靈活的兩線式分析儀。
-
四線式液體分析計 FLXA402
The FLEXA™ 系列分析計是模組化設計的分析計,用於工業裝定中的連續線上測量。提供單一或多sensor測量。
-
數位 SMART SENCOM™ 轉接器: SA11
可重複使用的 SMART 轉接器,只需在感測器達到其使用壽命時進行處理。橫河電機的SENCOM 4.0平台,可降低營運成本和資源浪費,同時貢獻永續未來的長期業務目標。
-
pH和ORP傳感器
pH電極和傳感器是進行pH值測量的傳感部分,有伸縮式、流通式、浸入式和直插式等多種安裝選項。選擇合適的pH電極/傳感器對優化測量結果至關重要。