Introduction
Wastewater from electroplating facilities and certain types of chemical plants contains toxic forms of hexavalent chromium such as chromate and dichromate. The hexavalent chromium in this wastewater must be reduced before the water can be discharged. This requires a two-step process: hexavalent chromium (CR6) is reduced to trivalent chromium (CR3); and CR3 is precipitated as chromium hydroxide. As the oxidation reduction potential (ORP) and the speed of the reduction reaction are closely tied to the pH value, ORP and pH analyzers are used to ensure proper control of the reduction process through such means as the injection of reducing agents.
pH and ORP measurements in these reaction tanks are complicated by the presence of chrome and sulfur dioxide, which can poison the sensor reference under certain circumstances. pH and ORP control in these applications may be conducted using alarm relays and a simple on/off control scheme such as available in the FLXA402 Analyzer. Alternatively, the 4-20mA current output can be used directly for proportional control, or sent to a distributed control system as needed. The FLXA21/FLXA202/FLXA402 can measure both ORP and pH. Both 2-wire and 4-wire analyzers are suitable for this measurement system. A gold electrode should be used for ORP measurement of chromium wastewater.
Reducing trivalent chromium process
Expected Benefits
- Measures pH/ORP of chromate wastewater continuously
- Reduces operating costs
Process Overview
First, hexavalent chromium, either in the form of chromate or dichromate, is reduced to trivalent chromium. Wastewater flows into the first reaction tank, where the pH is measured and sulfuric acid is automatically brought into the process until a pH set point value in the acidic range is achieved. The reaction time is just a few minutes, and a lower pH for an even faster reaction would require considerably more acid. At the same time, the oxidation reduction potential (ORP) of the solution is measured, and sulfur dioxide (SO2), sodium sulfite, or sodium metabisulfite is automatically injected until an ORP value of approximately 280 mV is achieved.
Then in the second tank, the pH is raised to 8.5 by the addition of an alkaline solution such as ammonia or caustic (NaOH), where it is converted to chromium hydroxide. The precipitate, although heavier than the water, does not drop to the bottom due to agitation in the tank. The mixed slurry flows to a settling tank, where the trivalent (Cr3+) chrome settles to the bottom and the clear chromium-free water flows over the tank for further treatment. Chemicals known as coagulants are sometimes added to the second reaction tank to help form larger particles and aid in sludge removal. The reducing agent may be a substance such as ferrous sulfate, sodium metabisulfite, or sulfur dioxide. Chemicals known as coagulants are sometimes added to the second reaction tank to help form larger particles and aid in sludge removal.
Solution Details
Measurement system
2-wire/4-wire pH/ORP measurement system
Sensor/Holder | |
---|---|
KCl refillable ORP sensor: | OR8EFG-AU-☐☐-TT1-☐*A |
KCl refillable pH sensor: | PH8EFP-☐☐-TN-TT1-N-☐*A |
Submersion type holder: | PH8HS-PP-☐☐-T-NN-NN*A |
Terminal box (when needed) | |
WTB10-PH1 | (for 2-wire system) |
WTB10-PH3 | (for 4-wire system) |
Converter/transmitter: | |
2-wire pH/ORP transmitter (pH+ORP 2 input): | FLXA21-D-P-S-☐☐-P1-P1-A-N-LA-N |
Distributor (for 2-wire system): | |
PH201G- A☐*C | |
4-Wire Converter (pH+ORP 2 input): | FLXA402-A-B-□□-P1-P1-□□-NR-N-N-N-NN |
- Check solutions for ORP analyzer
Oxidation-reduction potential of check solutions (quinhydrone/iron solutions)
A check solution is used to determine whether the ORP sensor is operating correctly. There are two types of check solutions: quinhydrone and iron.
Quinhydrone solution: approx. 200 to 300 mV
Iron solution: approx. 420 to 520 mV
Unlike a pH standard solution, an ORP check solution does not always indicate a constant reference value. Whether the sensor is operating normally can be determined by seeing whether its readings are within the acceptable range.
Preparation of a check solution (250 mL)
Quinhydrone solution: Dissolve the following reagent in pure water and dilute to 250 mL.
Quinhydrone salts: P/N K9024EC
Ferrous & ferric: dissolve the following reagent in a 2-mol/L sulfuric acid solution and dilute to 250 mL.
Ferrous & ferric salts: P/N K9024ED - Use of a gold electrode for ORP measurement
For ORP measurement of chromate wastewater, the use of a gold electrode is recommended.
Utilities
- FLXA21/FLXA202
Power supply: 23 to 40 V DC (from distributor) - PH201G distributor (for 2-wire system)
Power supply:
100 V: 20 to130 V DC/80 to 138 V AC, 47 to 63 Hz
220 V: 120 to 340 V DC/138 to 264 V AC, 47 to 63 Hz
Power consumption:
24 V DC: approx. 200 mA
100 V AC: approx. 7 VA
220 V AC: approx. 11 VA - FLXA402
Power supply: 90 to 264 V AC, 50/60 Hz
Power consumption: approx. 35 VA
업종
-
수처리
Yokogawa는 수처리 설비의 더욱 안정적인 운영을 위한 최적의 솔루션을 제공합니다. 이러한 솔루션에는 정교한 기술, 탁월한 제품 품질 및 라이프 사이클 전반에 걸친 광범위한 애플리케이션 노하우가 포함됩니다.
-
정수 및 하수 처리
Yokogawa는 보다 효율적인 사회를 만들기 위하여 에너지 최적화 기술 개발, 온실가스 감축, 오염 물질로부터 환경을 보호하는 견고한 제품 제작 등을 통해 지속 가능한 수자원 생산을 위한 제어 솔루션을 제공하고 있습니다. Yokogawa의 첨단 기술과 폭넓은 애플리케이션 노하우를 통해 고객과 협력하여 사업을 활성화하고 플랜트 수명주기 전반에 걸쳐 높은 가치를 제공할 수 있는 지속 가능한 솔루션을 제공합니다. 당사의 기술과 제품은 플랜트의 성능을 향상시키고 오늘날의 수자원 시장에서 경쟁적으로 운영할 수 있도록 보장하며 운영비를 절감합니다. Yokogawa는 지자체 및 공업용수 처리 시장에서 광범위한 수처리 응용 분야를 지원합니다.
-
폐수처리
폐수 처리 설비는 많은 모터, 펌프, 송풍기 등을 사용하기 때문에 운전 비용을 줄이기 위해서는 전력 소비를 줄이는 것이 중요합니다. Yokogawa는 에너지 효율성을 높이기 위한 최적의 제어 솔루션을 제공합니다.
Related Products & Solutions
-
2-Wire Transmitter/Analyzer FLXA202
The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.
-
2-Wire Transmitter/Analyzer FLXA202/21
FLEXA ™ 시리즈 분석기는 산업용 설비의 연속 온라인 측정에 사용됩니다. 단일 또는 이중 센서 측정 옵션이 있어 가장 유연한 2 선식 분석기입니다.
-
All-in-One pH/ORP Sensor Series FU20/FU24/PH20
PH20, FU20, FU24는 올인원 타입의 pH 와 ORP 센서로서 Yokogawa가 "Simple is best" 이라는 모토를 센서 기술에 어떻게 적용하는 지를 보여줍니다.
-
Digital SMART SENCOM™ Adapter, SA11
Reusable SMART adapter, requiring only the analog sensor to be disposed of when it reaches the end of its lifetime. With the SENCOM 4.0 platform, Yokogawa delivers reduced costs and waste while contributing to its long-term business goals of a sustainable future for all.
-
pH and ORP Analyzers
pH와 ORP 미터, 분석계 및 전송기는 수질/제품 품질을 보장하고 유출물 배출량, 배치 중화, 펄프 스톡, 세정기, 냉각 타워, 화학, 폐수 처리 및 기타 여러 어플리케이션의 연속 공정 모니터링에 사용합니다.
-
pH and ORP Sensors
pH 전극 및 센서는 pH 측정의 감지 부분입니다. Retractable, flow-though, 침적 및 직접 삽입을 포함한 다양한 설치 옵션이 있습니다.
적절한 pH 전극 / 센서 선택은 최적의 측정 결과를 위해 중요합니다.