pH/ORP Measurement for Reverse Osmosis

下载 (297 KB)

Background Information

Reverse osmosis

Processes requiring pure water must continually replace the water being consumed. Sources of replacement water are usually local supplies from a river or lake and therefore require pre-treatment and purification before it can be used in the process.

After preliminary purification which may include filtration, clarification and softening, further downstream, a two-pass reverse osmosis system and demineralization operations are typically employed to further purify the water.

Osmosis is the natural tendency of a fluid, usually water, to pass through a semipermeable membrane from a less concentrated solution into a more concentrated one, thus equalizing the concentrations on each side of the membrane.

In reverse osmosis (RO), pressure must be exerted on the side with the concentrated solution to force the water molecules across the semi-permeable membrane to the fresh (pure) water side.

This semi-permeable membrane inhibits the majority of dissolved impurities from passing through to the pure water side. The amount of impurities carried over depends on the type and condition of the membrane (i.e. age, cleanliness) and the amount of pressure applied (energy) to the process.

Not all the feed water passes through the membrane. Some is diverted to flow over them to cleanse away the rejected impurities in a cross-flow filtration mode.

The RO system produces one purified water stream called permeate and a second stream called concentrate, brine, or reject. Feedwater enters the machine at fairly low pressure and flows through pre-filters to remove suspended particles, such as silt. Pre-filters are typically a replaceable cartridge type which provides a cost effective method for keeping the membrane clean. Typical life expectancy for these membranes is approximately three years.

RO systems are designed for automatic operation and require routine preventative and corrective maintenance. Common problems include membrane fouling and the use of improper flow rates. The result is reduced throughput capacity and shortened runs.

Membranes can fail altogether, resulting in excessive demand on downstream purification systems and poor quality product water.

Both pH and conductivity measurements are used to safeguard the successful operation of an RO system.

Some types of RO membranes are sensitive to feed water pH and can become damaged if the pH is outside the recommended range of 5 to 8 pH. A pH sensor upstream of the membrane can provide a feedback signal to control dosing of acidic or basic reagent to maintain the pH within acceptable limits.

Conductivity measurements are used at both the inlet and outlet of the RO unit to determine whether the total dissolved solids are being filtered effectively.

General Applications

Reverse osmosis systems can remove up to 100% of suspended solids and approximately 90% of dissolved solids, dissolved silica, alkalinity and hardness.

A common use for RO is for purifying water, removing salts and other impurities to improve the color, taste and other properties. It is regularly used forcommercial and residential water filtration and is also one of the methods used for desalinization of seawater.

RO systems are capable of rejecting bacteria, salts, sugars, proteins, particles, dyes, and other constituents which have a molecular weight of greater than 150-250 Daltons.

The separation of ions with reverse osmosis is aided by charged particles. This means any dissolved ions which carry a charge, such as salts, are more likely to be rejected by the membrane than those that are not charged, such as organics. The larger the charge and the larger the particle, the more likely it will be rejected.

The majority of RO membranes are negatively charged when they are operated within the pH levels most commonly encountered in water applications.

Pure Water Applications

A two-pass RO system is typically installed upstream of the demineralizer. Its performance is pH dependent with the second-pass section most dramatically affected. While these changes are not significant in the majority of applications, variations become crucial to the success of high-purity water processing.

In addition, the effect of minor feedwater constituents, such as alkalinity and ammonia also play a role in achieving high-purity permeate.

The overall efficiency of dissolved solids removal is usually determined utilizing a pair of conductivity measurements, one at the inlet (cell 1) and one at the outlet (cell 2). This is referred to as % rejection and calculated by the formula:

% rejection = [1-(cell2)/(cell 1)] x 100

For example if the inlet water had 200 ppm of dissolved solids and the outlet water had 10 ppm, the efficiency would be 95% rejection rate. A typical range for this type of application is 80% - 100% rejection.

A final conductivity measurement after the 2nd stage is often used to determine the absolute quality of the outlet water.

Ammonia also affects the production of high purity water and may be present due to municipal chlorination of feedwater or from organic contamination.

Ammonia (NH3) will through the membrane system in either the molecular or ionic (NH4+) form.

 

pH/ORP Measurement for Reverse Osmosis

Ammonium hydroxide is less conductive than ammonium carbonate [(NH4)2CO3] so it is not uncommon to find off-line samples or storage tank water with conductivity higher than that of on-line readings.

The pH values will be lower. This shift in pH is due to absorption of CO2 from the air and the formation of carbonic acid in the water. Without the presence of ammonia, this type of contamination of high-purity water with CO2 would generate higher conductivity as well as the reduced pH.

 

Product Recommendations

pH Measurement System

Process Liquid Analyzer

  • 2-wire FLXA21 pH/ ORP Analzyer
  • 4-wire PH450G pH/ORP Analyzer

FLXA202 Two Wire pH and ORP AnlayzerPH450 Four wire pH and ORP Analyzers

Sensor Selection

Option #1:

Holders

  • FF20 Flow-thru assembly with individual measure, reference and temperature electrodes
  • FS20 Insertion assembly with individual measure, reference and temperature electrodes

Sensors

Bellowmatic reference electrode (SR20-AC32), coupled with the shock-proof measuring electrode (SM21-AG4) and Pt1000 temperature electrode (SM60-T1)

sensor

Option 2:

Holder: PH8HH Flow Thru assembly

Sensor: PH8EHP Flowing reference pH Sensor for High Purity Water

PH8HH Flow Thru assembly

 

Conductivity Measurement System

Process Liquid Analyzer

  • 2-wire FLXA21 Conductivity Analyzer
  • 4-wire SC450G Conductivity Analzyer

EXA450

Sensor Selection

Holders:

  • FF40 Flow Thru assembly
  • FS40 Insertion assembly

Electrodes

  • SC42-SP24
  • SC42-SP34

SC42

Note: For additional information on this application contact the local Yokogawa Process Liquid Analyzer Department

行业

相关产品&解决方案

Flow/NPT Fittings FF20/FS20

Yokogawa has invested considerable design and development time in producing a full range of fittings with particular emphasis on designs that reduce installation and maintenance time and consequently save operation costs.

FLXA202/21两线制变送器/分析仪

FLEXA系列分析仪用于工业设施中的连续在线测量。它是灵活的两线制分析仪,可选择单传感器或双传感器测量。

PH8EHP高纯水pH传感器

通过PH8EHP pH传感器和PH8HH支架能够可靠测量锅炉和半导体工艺应用中所用高纯水的pH值。

SC42/SC4A(J)接触式电导率传感器

测量水溶液的特定电导率对于确定水中的杂质越来越重要。横河电机设计了一系列精密传感器和仪器,即使在极端条件下也能应对这些测量。

四线制电导率分析仪

EXAxt450系列涵盖所有电导率应用,包括标准分析仪中的所有特殊软件功能,可减少配置数量。这样可以减少拥有多个电导率应用的用户库存和培训需求。

pH和ORP传感器

pH电极和传感器是进行pH值测量的传感部分,有伸缩式、流通式、浸入式和直插式等多种安装选项。选择合适的pH电极/传感器对优化测量结果至关重要。

pH和ORP分析仪

pHORP流量计、分析仪和变送器用于pHORP的连续过程监测,以确保水/产品质量,如监测污水排放、批量中和、浆料存储、洗涤塔,冷却塔、化学品、水/废水处理和许多其他应用。

电导率传感器

电导率传感器和电极用于测量过程电导率、电阻率、WIFI、软化水、RO水、百分比浓度、锅炉水排污和TDS。有伸缩式、流通式、浸入式和直插式等多种安装选项。选择合适的电极/传感器对优化测量结果至关重要。

电导率分析仪

电导率测量仪、分析仪和变送器用于对电导率、电阻率、WIFI、软化水、RO水、百分比浓度、锅炉水排污和TDS进行连续测量和监测。

×

Have Questions?

Contact a Yokogawa Expert to learn how we can help you solve your challenges.

置顶
WeChat QR Code
横河电机(中国)有限公司
WeChat Recruiting QR Code
横河电机中国招聘