Boiler Leak Detection and Ion Exchange Resin Monitoring at Power Station

下载 (275.6 KB)

Introduction

Seawater leak detection is one of the post-condensation water quality management processes that are performed for power station boilers and similar facilities. Damage to the ion exchange resin, which deionizes the supplied water, is also monitored during this process, and both of these applications are executed by a conductivity analyzer.

Expected Benefits

  • Detects seawater leakage and ion exchange resin damage
  • Reduces operating cost

Process Overview

Boiler Water Quality Management Process

Boiler Water Quality Management Process

The above illustration shows where analyzers are used in the boiler water quality management process.

In the measurement point iab-app-x-en.gif shown in the figure, two different signal ranges are needed for deionized water management and seawater leak detection. The FLXA402 can simultaneously generate output signals for two different ranges, meaning that a single unit can perform deionized water management concurrently with seawater leak detection.

Other applications for this conductivity analyzer include the management of deionized boiler water.

Solution Details

Boiler Leak Detection

Measurement system 4-wire conductivity system
Converter FLXA402-A-B-☐-C1-NN-A2-WR-☐-☐-☐-NN
Sensor SC4A(J)-S-AD-09-002-☐☐-T1/PS
General Specifications
FLXA402 4-wire Conductivity Converter
Measuring range (at process temperature; C: cell constant)
[Conductivity] Minimum: 0 µ/cm
Maximum: 200 mS/cm x C (overrange: 2000 mS/cm)
[Resistivity] Minimum: 0.005 kΩ/C
Maximum: 1000 MΩ·cm
[Temperature] Pt1000: -20 to +250°C
Output setting range
[Conductivity] Minimum: 0.010 µS/cm
Maximum: 2000 mS/cm
[Resistivity] Minimum: 0.001 kΩ·cm
Maximum: 1000 MΩ·cm
[Temperature] Min. span: 25°C; Max. span: 270°C
Output signal: two or four outputs of 4-20 mA DC + HART
Construction: for outdoor installation, IP66, NEMA Type4X waterproof
Ambient operating temperature: -20 to +55°C
Power supply voltage: 90 to 264 V AC, 50/60 Hz
Power consumption: 35 VA maximum
SC4A(J) Conductivity Sensor
Electrode system: two-electrode system
Cell constant: 0.02 cm-1
Measuring range: 0 – 0.5 µS/cm to 0 – 200 µS/cm
Temperature range: 0 - 110°C
Wetted material: SUS316L, PEEK (polyether ether ketone) /PS Adapter (option code of SC4A(J))
Material: SUS316L
Operating pressure: 1 MPa maximum (depends on the SC4A(J) Sensor)

相关行业

  • 电力

    20世纪70年代中期,横河电机通过推出EBS电气控制系统进入了电力业务领域。自此以后,横河电机坚定不移地持续开发其技术和能力,旨在为全球客户提供更优的服务和解决方案。

  • 热电联产

    热电联产或CHP是从单一燃料源产生电能和热能的有效方法。

  • 联合循环

    在各地天然气供应充足的地区,正在建立越来越多的联合循环发电厂。

  • 火电

    使用煤、石油或天然气作为燃料的火力发电占发电量的大部分。

相关产品&解决方案

  • 2-Wire Transmitter/Analyzer FLXA202

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

  • 2-Wire Transmitter/Analyzer FLXA21

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

  • FLXA402多通道四线制分析仪

    FLEXA™系列分析仪是模块化设计的分析仪,用于在工业设施中进行连续在线测量。可提供单传感器或多传感器测量。

     

  • SC42/SC4A(J)接触式电导率传感器

    测量水溶液的特定电导率对于确定水中的杂质越来越重要。横河电机设计了一系列精密传感器和仪器,即使在极端条件下也能应对这些测量。


置顶
WeChat QR Code
横河电机(中国)有限公司