Advanced Diagnostic Functions of EJX Series Differential Pressure/ Pressure Transmitters

Загрузить (1.6 MB)

Kiyoshi Watanabe1

Diagnosing the process interface where the field instruments and process equipment are contacting each other enables prediction of the required maintenance for the instrumentation. With the EJX series differential pressure/pressure transmitters, Yokogawa has developed functions to detect blockage and monitor heat traces in impulse lines which are process interface parts. These functions are called advanced diagnoses, to distinguish them from the self-diagnosis of the instruments. This paper introduces the advanced diagnostic functions built in the FOUNDATION Fieldbus communication type and HART communication type EJX series transmitters.

  1. Field Instruments Business Center, Industrial Automation Business Headquarters

INTRODUCTION

 Figure 1 Configuration of Diagnostic Functions in EJX Series
Figure 1 Configuration of Diagnostic
Functions in EJX Series

Field instruments are expected to be equipped with diagnostic functions to predict abnormal process conditions, and are also expected to expand these functions. The ability to extract diagnostic information for prediction and prevention from various physical process quantities measured by devices and make it available allows the user to reduce non-essential and non-urgent maintenance and thus cut maintenance costs. There are high expectations for field instruments to improve diagnostic functions to facilitate the management of devices and plant operations and help cut maintenance costs1.

Yokogawa's EJX series differential pressure/pressure transmitter provides diagnostic functions to detect blockage in impulse lines and monitor heat traces for the process interface, a point where the devices and process equipment contact and interact. The diagnostic function consists of two functions, and both of them are related to impulse lines that is used to transmit the process fluid pressures to the transmitter. The one utilizes slight pressure fluctuations of the fluid to detect a blockage in the impulse lines. The other utilizes the temperature gradient corresponding to the thermal resistance inside the transmitter to estimate and monitor the status of heating equipment that is installed to prevent the fluid in the lines from freezing. These functions are called advanced diagnostic functions to differentiate them from the self-diagnostic functions of the device. Figure 1 shows the configuration of the diagnostic functions. The principles and details of the functions are described in Yokogawa technical report2 3. This report focuses on the expansion of the implementation of the functions to other models.

OVERVIEW OF ADVANCED DIAGNOSTIC FUNCTIONS

Figure 2 Installation of Impulse Lines for Differential Pressure
Figure 2 Installation of Impulse Lines for Differential
Pressure Transmitter and Attenuation of Fluctuations

The advanced diagnostic functions of the EJX series comprise multi-sensing (differential pressure, static pressure, and temperature measurements) characterizing the instruments and detection of abnormal conditions by monitoring the process environment applying proprietary algorithms.

Impulse Line Blockage Detection

A differential pressure/pressure transmitter measures pressures of process fluids that flow in the line, along with fluctuations caused by pumps or the like. Blockage is detected by utilizing the property that the fluctuations attenuate when the impulse line is blocked; specifically, by extracting the fluctuation components from the differential pressure/pressure values, comparing the degree of attenuation with the reference values obtained in normal operation, and making a judgment.

Figure 2 shows a typical installation of the impulse lines for a differential pressure transmitter and a schematic diagram showing the attenuation of fluctuations.

Heat Trace Monitoring

The soundness of the temperatures of the steam, heater etc. that keep the impulse lines warm is monitored by using the flange temperature estimated from the temperatures of the capsule and amplifier of the transmitter. Figure 3 shows a typical installation using a bundle tube for preventing freezing, and Figure 4 shows an estimation of the flange temperature from the capsule and amplifier temperatures.

Figure 3 Freeze Prevention Using Bundle Tube
Figure 3 Freeze Prevention Using Bundle Tube

APPLICATION OF ADVANCED DIAGNOSTIC FUNCTIONS TO EJX SERIES

Figure 4 Estimation of Flange Temperature from Capsule
Figure 4 Estimation of Flange Temperature
from Capsule and Amplifier Temperatures

The EJX series is capable of independently detecting four modes of impulse line blockage: both side, high-pressure side, low-pressure side, and either one side by utilizing a multi-sensing function of a silicon resonant sensor capable of simultaneously measuring differential pressure, high-pressure- side static pressure, and low-pressure-side static pressure4. The EJX can be used not only for differential pressure but also for level and pressure measurements and is able to detect blockages in the impulse line on the pressure measurement side applying the same principle. The EJX is also able to monitor the flange temperature, even if the flange shape varies, because it estimates the flange temperature from the capsule and amplifier temperatures.

The EJX series consists of models designed for differential pressure, pressure, and level measurement applications. Since the diagnostic functions are not limited by the measurement applications, they are implemented in all the models supporting the FOUNDATION Fieldbus and HART communication protocols. Table 1 shows the blockage detection items for each EJX series model.

Table 1 EJX Models and Applicable Blockage Detection Items

Models Names Blockage Detection Items
EJX110/130 Differential Pressure Transmitter Both-side blockage
High-pressure-side blockage
Low-pressure-side blockage
One-side blockage
EJX118 Diaphragm Sealed Differential Pressure Transmitter
EJX210 Flange Mounted Differential Pressure Transmitter
EJX115 Low Flow Transmitter
EJX910/930 Multivariable Transmitter
EJX120 Draft Range Differential Pressure Transmitter (for the both-side or one-side blockage only)
EJX430/440 Pressure Transmitter Impulse line blockage on the pressure measurement side
EJX310 Absolute Pressure Transmitter
EJX438 Diaphragm Sealed Pressure Transmitter
EJX510/530 EJX610/630 Pressure Transmitter (Screw Type)

ADVANCED DIAGNOSTIC FUNCTION SPECIFICATIONS

Table 2 shows the specifications of the advanced diagnostic functions. The specifications of the diagnostic functions are the same between the two communication types except for the alarm output destination of the diagnostic results, the number of alarm setting items and others.

Table 2 Advanced Diagnostic Function Specifications

Diagnostic Functions Communication Types
FOUNDATION Fieldbus HART
Impulse Line Blockage Diagnosis Pressure Fluctuation Measurement Period 100 msec 135 (100) msec
Diagnostic Period 20 to 65535 sec
Diagnostic Mode Suspend diagnosis, acquire reference value, execute diagnosis
Alarm Setting Items 12 (11) items 11 items
Diagnostic Alarm Output Communication [AIFB]
LCD display
Communication
LCD display
4-20 mA signal
Contact output
Heat Trace Monitoring Diagnosis Temperature Measurement Period 1 sec
Diagnostic Period 1 sec
Flange Temperature Output Communication [STB, AIFB]
LCD display
Communication
Alarm Setting Items None (2 items) 2 items
Diagnostic Alarm Output Communication [AIFB]
(Communication [STB, AIFB])
(LCD display)
Communication
LCD display
4-20 mA signal
Contact output

AIFB: Analog Input Function Block
STB: Sensor Transducer Block
Note: Figures in parentheses for EJX910/930

ADVANCED DIAGNOSTIC PROCESSING

Figure 5 shows the flow of the advanced diagnostic processing and Table 3 shows the output related to the corresponding diagnosis.

Figure 5 Advanced Diagnostic Processing Flow 

Figure 5 Advanced Diagnostic Processing Flow

Table 3 Diagnosis-related Output

  Output Destinations/Output Signal Parameters Descriptions
FOUNDATION Fieldbus Communication Type HART Communication Type
(1) VALUE_□ Fluct Variables (Fluctuation Values)
Diag Variables (Degree of Blockage)
Fluctuation values and a degree of blockage of differential pressure, high-pressure-side static pressure, and low-pressure-side static pressure
REFERENCE_□ Diag Reference Fluctuation reference values for differential pressure, high-pressure-side static pressure, and low-pressure-side static pressure
(2) DIAG_ERR Diag Error Diagnostic results of impulse line blockage and heat trace monitoring
(3) DEVICE_STATUS Device Status
Status Group
Description of the alarm detected as the diagnostic results.
In case of HART communication type, Device Status is a representative notification and Status Group is a detailed notification.
(4) DIAG_H_ALM, DIAG_L_ALM High-pressure-side and low-pressure-side discrete alerts resulting from blockage detection
(5) PV, SV, TV → AI. OUT The blockage detection result is added to the status of the process value.
The result is reflected in the OUT signal status of the AI function block.
(6) LCD Display LCD Display The detected alarm is displayed on the LCD.
(7) Analog Output The detection result is reflected in the 4-20 mA analog signal output.
(8) Digital Output The detection result is reflected in the contact output.

Remark: The auxiliary parameter name indicating the fluctuation value or a degree of blockage is placed in □.

The impulse line blockage diagnosis calculates the pressure fluctuations of the differential pressure, high- pressure-side static pressure, and low-pressure-side static pressure every 100 milliseconds or 135 milliseconds, and performs statistical processing as well. Diagnosis and blockage detection are performed for every diagnostic period by combining the two kinds of variables: a fluctuation ratio of the reference value and diagnosing value and a degree of blockage that is obtained from the correlation of the fluctuations. The diagnostic period can be changed by the setting.

The heat trace monitoring diagnosis calculates the flange temperature from the capsule and amplifier temperatures every second and makes a judgment by comparing the value with the high and low threshold values.

While the diagnosis makes a judgment of all the items, the required diagnostic items are selected and the result is output according to the alarm output setting for the diagnostic result.

With the FOUNDATION Fieldbus communication type, the diagnostic alarm is reflected not only in the status output but also in the OUT signal of the AI function block. With the HART communication type, not only the Burnout and Fallback output by the 4-20 mA analog signal but also contact output is available. The following describes the main processing procedures.

Processing Procedures for Impulse Line Blockage Diagnosis

 Figure 6 Alarm Masking
Figure 6 Alarm Masking (for HART Communication Type)

The fundamental element of the blockage diagnosis is monitoring of the pressure fluctuations. A blockage is detected by comparing the current process fluctuation value with the reference fluctuation value in the normal state. Generally, when the differential pressure and static pressure are high, the fluctuations are also large so detection is stable. However, when levels or pressures are measured, when measured fluid is highly viscous fluid of which viscosity is larger than 10 centistokes (cSt), or when measured fluid is a gas, the fluctuations are not large enough to detect the blockage correctly. In this case, a diagnostic result error occurs, indicating that the diagnostic result is inadequate.

The blockage diagnosis is performed in the order of the acquisition of the reference values, confirmation of the blockage detection by the simulated blockage, and actual blockage detection. When obtaining reference values, it is confirmed that the fluctuations are large enough. A minimum limit to the fluctuation value for the diagnosis is specified. The diagnosis is possible only when the fluctuation is larger than the limit.

 Figure 7 Example of DTM Diagnostic GUI
Figure 7 Example of DTM Diagnostic GUI

The setting of the diagnostic functions and confirmation of the parameters are performed using setting tools, such as Yokogawa's Integrated Device Management Software Package PRM (Plant Resource Manager) and Versatile Device Management Wizard FieldMate5 6. Since the reference values are acquired by switching modes in the device, another measuring instrument is not required. The blockage detection is confirmed by simulating a blockage by operating the three-way valve or stop valve installed on the impulse line and generating an alarm.

Processing Procedures for Heat Trace Monitoring Diagnosis

Since the flange temperature is estimated from the capsule and amplifier temperatures, a coefficient for calculating the flange temperature needs to be obtained. The coefficient is obtained by heating the flange and measuring its temperature before diagnosis, and then the obtained coefficient and the high and low temperature alarm threshold values are set for the device.

Processing Procedures for Alarm Masking

Figure 6 shows the masking of diagnostic alarms for the HART communication type. The diagnostic results of blockage detection and flange temperature error are kept in the Diag Error parameter and the output and display of the results are determined by the Diag Option parameter. With the FOUNDATION Fieldbus communication type, the diagnostic results are kept in the DIAG_ERR parameter, and the selection and output are subject to the DIAG_OPTION parameter.

GUI FOR ADVANCED DIAGNOSTIC

Device Type Manager (DTM) of the FieldMate is equipped with a dedicated diagnostic graphic user interface (GUI) as shown in Figure 7, which facilitates the setting and monitoring of parameters for the advanced diagnosis. The GUI makes it easy to obtain a blockage diagnostic reference value, calculate the flange temperature coefficient, and select the alarm masking.

Alarm occurrences and their description can be confirmed on the Diagnostic Information screen in Device Viewer of the FieldMate. Fluctuation values and a degree of blockage can be monitored on the Trend Information screen. Figure 8 shows those screen examples. Changes in the diagnostic data caused by operating the valve can be viewed graphically when confirming the simulated blockage detection for the blockage diagnosis.

CONCLUSION

 Figure 8 Examples of Diagnostic Information and Trend
Figure 8 Examples of Diagnostic Information
and Trend Information Screens in Device Viewer

Archiving diagnostic information on the device described in this report in an application of the upper system and analyzing its long-term trend enable monitoring the tendency and performing accurate predictive diagnosis. This can be accomplished by combining the EJX series differential pressure/pressure transmitters and Yokogawa's Integrated Device Management Software Package PRM.

In order to cope with a growing number of devices and an increasing amount of information, new functions similar to those mentioned so far must be performed by the field instrument itself, and also incorporation of predictive diagnostic functions into the field instrument, improvement of the functionality and accuracy, and development of new techniques will be required in future. Yokogawa will not only respond to these requirements but also provide higher value- added solutions combining Yokogawa's system products.

REFERENCES

  1. Toshio Aga, "Future Technical Prospects for Field Instruments," Yokogawa Technical Report, Vol. 48, No. 1, 2004, pp. 11-12 in Japanese
  2. Nobuo Miyaji, Kaoru Sonoda, Hideo Akahori, et al., "Impulse Line Blocking Diagnosis of Differential Pressure Transmitters," Yokogawa Technical Report, Vol. 48, No. 1, 2004, pp. 33-36 in Japanese
  3. Yoshitaka Yuuki, Nobuo Miyaji, et al., "Advanced Field Diagnosis to Achieve Asset Excellence," Yokogawa Technical Report English Edition, No. 44, 2007, pp. 17-20
  4. Akio Itou, Shin-ichi Mimura, et al., "EJX910 Multivariable Transmitter," Yokogawa Technical Report English Edition, No. 42, 2006, pp. 13-16
  5. Shunsuke Hayashi, "Unified Diagnoses Management of PRM Plant Resource Manager," Yokogawa Technical Report English Edition, No. 44, 2007, pp. 21-24
  6. Isao Hirooka, Youji Saitou, et al., "FieldMate Field Device Management Tool for the New Era," Yokogawa Technical Report English Edition, No. 44, 2007, pp. 9-12
  • EJX, PRM, and FieldMate are registered trademarks of Yokogawa Electric Corporation.
  • FOU NDATION Fieldbus and HART are registered trademarks of the Fieldbus FOUNDATION and the HART Communication Foundation (HCF), respectively.

Отрасли

  • Вода и сточные воды

    Водные ресурсы истощимы, поэтому содействие устойчивому водному циклу является одной из Целей устойчивого развития (SDG). Компания Yokogawa предоставляет передовые решения в области цифрового управления для стабильной подачи чистой и безопасной воды, очистки сточных вод с целью защиты водной среды, управления потерями воды и оптимизации работы установок с целью сокращения выбросов CO2 и снижения эксплуатационных расходов. Используя наши передовые технологии, надёжные продукты, обширные знания и опыт реализации различных проектов в сфере использования водных ресурсов, мы работаем с Вами, чтобы предоставлять устойчивые решения в сфере водных ресурсов, которые способствуют развитию Вашего бизнеса и повышают ценность на протяжении всего жизненного цикла оборудования.

    Компания Yokogawa поддерживает широкий спектр областей применения наших решений по обеспечению необходимого водного режима для рынков городского и промышленного потребления воды.

      

     

    Узнать больше
  • Геотермальная энергия

    Используя экологически чистую и стабильную геотермальную энергию можно вырабатывать электроэнергию на протяжении многих лет независимо от погодных условий. Yokogawa участвовала в десятках геотермальных энергетических проектов в Японии, Юго-Восточной Азии, Африке и других регионах, предоставляя различные технологии измерения и управления.

    Узнать больше
  • Нефтехимия и базовые химические продукты большого объёма

    Что бы вы не производили, нефтехимические, неорганические или промежуточные продукты, любая химическая компания находятся под постоянным давлением величин затрат и получаемой маржи в процессе обеспечения своевременной и эффективной поставки своей продукции заказчикам, сохраняя требуемый уровень безопасности и соблюдая необходимые нормативы. В дополнение к этому, производителям требуется постоянно подстраиваться к колебанию цен на энергоносители и сырьевой материал, чтобы обеспечить поставку самых маржинальных комбинаций продуктов на рынок.

    Компания Yokogawa обеспечивает потребности производств базовой химической продукции по всему миру и является признанным лидером в отрасли. С набором профильной продукции, решений и экспертных знаний, наша компания понимает ваши производственные потребности и сможет помочь Вам, работая вместе с вами и обеспечивая надёжные и выгодные решения на протяжении всего жизненного цикла Ваших производственных активов.

    Узнать больше
  • Электроэнергетика

    В середине 1970-х годов компания Yokogawa вошла в энергетический бизнес, выпустив электросистему управления EBS. С тех пор компания Yokogawa неуклонно продолжает развивать свои технологии и возможности для предоставления лучших услуг и решений нашим заказчикам по всему миру.

    Компания Yokogawa создала глобальную сеть решений в области электроэнергетики, чтобы играть более активную роль на динамично развивающемся мировом рынке электроэнергии. Это позволило наладить более тесную командную работу внутри компании Yokogawa, объединив наши глобальные ресурсы и отраслевые ноу-хау. Эксперты компании Yokogawa в области электроэнергетики работают вместе, чтобы предоставить каждому заказчику решение, которое наилучшим образом соответствует его сложным требованиям.

    Узнать больше

Related Products & Solutions

  • EJX118A

    Преобразователь дифференциального давления с выносными разделительными мембранами серии EJX-A.

    Узнать больше
  • EJX210A

    Преобразователь дифференциального давления серии EJX-A, монтируемый на фланце, разработан для определения уровня жидкости.

    Узнать больше
  • EJX438A

    Преобразователь избыточного давления с выносной разделительной мембраной на базе Серии EJX-A.

    Узнать больше
  • EJX440A

    Преобразователь избыточного давления традиционного монтажа на базе Серии EJX-A.

    Узнать больше
  • EJX630A

    Высокоэффективный датчик избыточного давления ввертного типа на базе Серии EJX-A.

    Узнать больше
  • EJX910A

    Этот преобразователь точно измеряет перепад давления, статическое давление и температуру процесса; затем использует эти значения в высокопроизводительном встроенном вычислителе расхода для расчета полностью компенсированного массового расхода.

    Узнать больше
  • EJX930A

    Этот преобразователь специально разработан для применения с высоким статическим давлением и позволяет точно измерять перепад давления, статическое давление и температуру процесса; затем использует эти значения в высокопроизводительном встроенном вычислителе расхода для расчета полностью компенсированного массового расхода.

    Узнать больше
  • Датчики давления

    Точное и стабильное измерение давления технологического процесса с помощью датчиков давления Yokogawa обеспечивает безопасную, надежную и прибыльную работу ваших установок.

    Узнать больше

Наверх