pH/ORP Measurement for Reverse Osmosis

下载 (418.5 KB)

Background Information

Reverse osmosis

Processes requiring pure water must continually replace the water being consumed. Sources of replacement water are usually local supplies from a river or lake and therefore require pre-treatment and purification before it can be used in the process.

After preliminary purification which may include filtration, clarification and softening, further downstream, a two-pass reverse osmosis system and demineralization operations are typically employed to further purify the water.

Osmosis is the natural tendency of a fluid, usually water, to pass through a semipermeable membrane from a less concentrated solution into a more concentrated one, thus equalizing the concentrations on each side of the membrane.

In reverse osmosis (RO), pressure must be exerted on the side with the concentrated solution to force the water molecules across the semi-permeable membrane to the fresh (pure) water side.

This semi-permeable membrane inhibits the majority of dissolved impurities from passing through to the pure water side. The amount of impurities carried over depends on the type and condition of the membrane (i.e. age, cleanliness) and the amount of pressure applied (energy) to the process.

Not all the feed water passes through the membrane. Some is diverted to flow over them to cleanse away the rejected impurities in a cross-flow filtration mode.

The RO system produces one purified water stream called permeate and a second stream called concentrate, brine, or reject. Feedwaterenters the machine at fairly low pressure and flows through pre-filters to remove suspended particles, such as silt. Pre-filters are typically a replaceable cartridge type which provides a cost effective method for keeping the membrane clean. Typical life expectancy for these membranes is approximately three years.

RO systems are designed for automatic operation and require routine preventative and corrective maintenance. Common problems include membrane fouling and the use of improper flow rates. The result is reduced throughput capacity and shortened runs.

Membranes can fail altogether, resulting in excessive demand on downstream purification systems and poor quality product water.

Both pH and conductivity measurements are used to safeguard the successful operation of an RO system.

Some types of RO membranes are sensitive to feed water pH and can become damaged if the pH is outside the recommended range of 5 to 8 pH.A pH sensor upstream of the membrane can provide a feedback signal to control dosing of acidic or basic reagent to maintain the pH within acceptable limits.

Conductivity measurements are used at both the inlet and outlet of the RO unit to determine whether the total dissolved solids are being filtered effectively.

General Applications

Reverse osmosis systems can remove up to 100% of suspended solids and approximately 90% of dissolved solids, dissolved silica, alkalinity and hardness.

A common use for RO is for purifying water, removing salts and other impurities to improve the color, taste and other properties. It is regularly used for commercial and residential water filtration and is also one of the methods used for desalinization of seawater.

RO systems are capable of rejecting bacteria, salts, sugars, proteins, particles, dyes, and other constituents which have a molecular weight of greater than 150-250 Daltons.

The separation of ions with reverse osmosis is aided by charged particles. This means any dissolved ions which carry a charge, such as salts, are more likely to be rejected by the membrane than those that are not charged, such as organics. The larger the charge and the larger the particle, the more likely it will be rejected.

The majority of RO membranes are negatively charged when they are operated within the pH levels most commonly encountered in water applications.

Pure Water Applications

A two-pass RO system is typically installed upstream of the demineralizer. Its performance is pH dependent with the second-pass section most dramatically affected. While these changes are not significant in the majority of applications, variations become crucial to the success of high-purity water processing.

In addition, the effect of minor feedwater constituents, such as alkalinity and ammonia also play a role in achieving high-purity permeate.

The overall efficiency of dissolved solids removal is usually determined utilizing a pair of conductivity measurements, one at the inlet (cell 1) and one at the outlet (cell 2). This is referred to as % rejection and calculated by the formula:

% rejection = [1-(cell2)/(cell 1)] x 100

For example if the inlet water had 200 ppm of dissolved solids and the outlet water had 10 ppm, the efficiency would be 95% rejection rate. A typical range for this type of application is 80% - 100% rejection.

A final conductivity measurement after the 2nd stage is often used to determine the absolute quality of the outlet water.

Ammonia also affects the production of high purity water and may be present due to municipal chlorination of feedwater or from organic contamination.

Ammonia (NH3) will through the membrane system in either the molecular or ionic (NH4+) form.

 

pH/ORP Measurement for Reverse Osmosis

Ammonium hydroxide is less conductive than ammonium carbonate [(NH4)2CO3] so it is not uncommon to find off-line samples or storage tank water with conductivity higher than that of on-line readings.

The pH values will be lower. This shift in pH is due to absorption of CO2 from the air and the formation of carbonic acid in the water. Without the presence of ammonia, this type of contamination of highpurity water with CO2 would generate higher conductivity as well as the reduced pH.

 

Product Recommendations

Process Liquid Analyzer:

  • 2-wire FLXA202 Analyzer
  • 4-wire FLXA402 Analyzer

FLXA202/FLXA21, FLXA402 pH/ OPR Analyzers

pH Measurement Sensor Selection:

Option #1:

Holders

  • FF20 Flow-thru assembly with individual measure, reference and temperature electrodes
  • FS20 Insertion assembly with individual measure, reference and temperature electrodes

Sensors

  • Bellowmatic reference electrode (SR20-AC32)
  • Shock-proof measuring electrode (SM21-AG4)
  • Pt1000 temperature electrode (SM60-T1)

sensor

Option 2:

Holder: PH8HH Flow Thru assembly

Sensor: PH8EHP Flowing reference pH Sensor for High Purity Water

PH8HH Flow Thru assembly

 

Conductivity Measurement Sensor Selection:

Holders

  • FF40 Flow-thru assembly
  • FS40 Insertion assembly

Electrodes

  • SC42-SP24
  • SC42-SP34

SC42

Digital SMART Option:
The re-usable smart adapter, SA11, offers full measuring parameter functionality of analog sensors equipped with a Variopin connector and Yokogawa ID chip. The SA11 automatically recognizes the installed sensor and prepares the right configuration.

The re-useable smart adapter, SA11

Note: For additional information on this application contact the local Yokogawa Process Liquid Analyzer Department

相关行业

  • 水和废水

    横河电机通过开发更节能的技术,帮助减少运营的碳排放,以及构建保护环境免受污染的坚固建筑,为可持续水生产提供控制解决方案。横河凭借先进的技术和广泛的应用专业知识与客户合作,提供可持续水生产的解决方案,促进客户的业务,并让整个工厂在生命周期中增加效用。横河的技术和产品可提高工厂的性能,确保它们在当今的水处理领域中具有竞争力,并降低运营成本。横河支持市政和工业水处理领域的各种水控制方面的应用。

  • 电力

    20世纪70年代中期,横河电机通过推出EBS电气控制系统进入了电力业务领域。自此以后,横河电机坚定不移地持续开发其技术和能力,旨在为全球客户提供更优的服务和解决方案。

  • 石油和天然气

    横河电机在石油天然气行业的各个环节均拥有丰富经验,业务覆盖海上与陆上设施、管道运输、终端处理及深水作业等领域。我们提供的解决方案能够提升安全水平、确保设备准确可靠地运行,并有效提高工厂运营效率。

  • 油气下游

    近年来,石油天然气下游行业正面临日益增多的挑战。这些挑战包括:需处理的原料特性不断变化、工艺设施与设备逐渐老化、能源成本持续攀升、能够安全高效运营炼油厂的熟练操作人员紧缺,以及市场和客户需求的快速变化。

    多年来,横河电机与众多下游企业携手合作,提供专注于解决这些挑战与难题的工业解决方案。横河电机的 VigilantPlant解决方案助力工厂业主实现工厂内的更大盈利和可持续安全运营。

  • 造纸

    面对不断变化的市场需求,造纸行业的竞争也愈演愈烈。横河电机可以帮助节能工厂实现可持续性发展。

  • 食品和饮料

    在横河电机,我们了解当今的食品和饮料公司在气候变化、消费者需求和竞争力增强方面面临着挑战。克服这些挑战需要创新的解决方案,需要关注生产、资产管理以及食品安全和质量等关键领域。

  • 化工

    化工厂存在连续生产与批次生产两种流程,两者对控制系统需求各异。连续工艺要求控制系统具备高稳定性与可靠性,避免因故障导致生产线停机;而批次工艺则强调灵活调整配方、工序等参数的能力。两类系统均需实现产品质量追溯管理,并支持非常规操作执行。横河电机凭借丰富的产品组合、资深系统工程师团队及全球销售服务网络,可为不同工艺流程提供定制化解决方案。

  • 炼油

    在不断变化的市场环境中,炼油厂不仅被视为原油加工单元,更是利润中心。与此同时,业界对这些设施的安全需求保持着高度重视。要实现长期盈利、效率提升与环境保护的目标,需要一套涵盖规划、调度、管理与控制的完整生产解决方案。凭借在自动化领域多年的专业积淀,横河电机能够为您提供高性价比的整体解决方案,助力提升运营效能,共创更清洁的世界。

  • 海上设施(FPSO、FLNG与FSRU)

    海上勘探与生产需要在严苛环境下实现更长运行时间。有人与无人设施需配备具备先进远程监控功能的可靠集成控制与安全系统(ICSS)。横河电机拥有先进技术及执行各种规模与复杂程度海上项目的丰富经验。

  • 上游

    上游行业涵盖海上和陆上作业,包括井口自动化、分馏、完井和分离等环节,旨在开采并初步处理地下或水下原油与天然气。

    石油被采至地表后,必须在运输前进行分离。通常在初级和二级分离阶段,通过三相分离将气流、水流和油流分开。气体输送需要管道,并可在上游阶段加入分馏处理。液体则存入储罐或通过管道输送至加工环节,此过程需准确的液位测量。

相关产品&解决方案

  • FLXA402多通道四线制分析仪

    FLEXA™系列分析仪是模块化设计的分析仪,用于在工业设施中进行连续在线测量。可提供单传感器或多传感器测量。

     

  • Flow/NPT Fittings FF20/FS20

    Yokogawa has invested considerable design and development time in producing a full range of fittings with particular emphasis on designs that reduce installation and maintenance time and consequently save operation costs.

  • PH8EHP高纯水pH传感器

    通过PH8EHP pH传感器和PH8HH支架能够可靠测量锅炉和半导体工艺应用中所用高纯水的pH值。

  • SC42/SC4A(J)接触式电导率传感器

    测量水溶液的特定电导率对于确定水中的杂质越来越重要。横河电机设计了一系列精密传感器和仪器,即使在极端条件下也能应对这些测量。

  • pH和ORP传感器

    pH电极和传感器是进行pH值测量的传感部分,有伸缩式、流通式、浸入式和直插式等多种安装选项。选择合适的pH电极/传感器对优化测量结果至关重要。

  • pH和ORP分析仪

    pH和ORP流量计、分析仪和变送器用于pH和ORP的连续过程监测,以确保水/产品质量,如监测污水排放、批量中和、浆料存储、洗涤塔,冷却塔、化学品、水/废水处理和许多其他应用。

  • 两线制变送器/分析仪FLXA21

    FLEXA™ 系列分析仪用于工业装置中的连续在线测量。可选配单传感器或双传感器测量,是现有非常灵活的两线制分析仪。

  • 电导率传感器

    电导率传感器和电极用于测量过程电导率、电阻率、WIFI、软化水、RO水、百分比浓度、锅炉水排污和TDS。有伸缩式、流通式、浸入式和直插式等多种安装选项。选择合适的电极/传感器对优化测量结果至关重要。

  • 电导率分析仪

    电导率测量仪、分析仪和变送器用于对电导率、电阻率、WIFI、软化水、RO水、百分比浓度、锅炉水排污和TDS进行连续测量和监测。


置顶
WeChat QR Code
横河电机(中国)有限公司