Gas Detection Easier with Yokogawa Wireless Gateways

다운로드 (191 KB)

Using Wireless for Gas Detection Is a Very Flexible Method, and Allowed ExxonMobil to Establish it as a Redundant System

by Jim Montague

Bin Xu
"We wanted to examine wireless because it's faster to install and costs less to deploy compared to a hardwired solution," said Bin Xu, instrumentation control engineer, Exxon Mobil. "This cost benefit could be particularly attractive for a brownfield project."

Finding tiny, significant or potentially hazardous gas sources is an essential safety capability in many process applications, but just sensing is no good unless those signals and data can be delivered to people and systems that need them.

To help advance efforts to provide better protection, ExxonMobil Upstream Research Co. is investigating the use of wireless components to get gas indications where they need to go. Bin Xu, an instrumentation control engineer at ExxonMobil, recently sought to demonstrate and verify the feasibility and reliability of a battery-operated, IS A100 wireless gas detection system with a redundant gateway at Exxon's lab in Houston.

"We wanted to examine wireless because it's faster to install and costs less to deploy compared to a hard-wired solution," said Xu. "Also, this cost benefit could be particularly attractive for a brownfield project."

Xu presented "Wireless Gas Detection Test for Safety Applications" today at the 2014 Yokogawa Users Group Conference and Exhibition in Houston.

"Overall, we installed three GS01 gas detectors from Norway-based GasSecure with a redundant YFGW 410 wireless gateway system and YFGW 510 transmitter from Yokogawa at an ExxonMobil site," explained Xu. "The wireless protocol we used is IS A100.11a, which uses a Modbus interface into the control system. Initially, we collected wireless data without feeding it into our safety system. Also, all three instruments were installed right next to existing wired gas detectors for comparison, and sensor and network performances were tracked as well." IS A100 just became a global IEC standard last week.

Xu added that the wireless-enabled gas detection system was configured all the way to a Modbus tag and was plug-and-play for ExxonMobil's site. The test system's gateway and instruments were pre-tested by GasSecure and were shipped from Norway directly to ExxonMobil. "The trick is to complete commissioning as simply as possible, so we asked the vendor to configure these components all the way to the gateway and make sure this was done before shipping to us," said Xu. "We asked each supplier to do the same. We provided parameters, IP addresses and other needed details, they did the configuration, and then we could just do the interface. This made our wireless system easier to set up and made it simple for us to pull diagnostic information into our other systems."

In addition to the savings, Xu added that using wireless for gas detection is also a very flexible method and even allowed him to establish it as a redundant system. "You just have to make sure that your device doesn't go beyond the capabilities of the gateway," said Xu. "This system could also be used in a SIL 2 application. We asked for and used Profisafe networking and were able to get this project up and running in just six weeks, which was a lot quicker than we expected. We want to promote wireless for safety in oil and gas applications, and what we really need to make it happen is standards like IS A100 and common guidelines and experiences—the more prescriptive, the better."

업종

  • 업스트림

    업스트림(Upstream) 산업에는 유전 또는 해저의 원유 및 천연가스의 채취 및 생산을 위한 유정제어, 증류, 분리 및 제품 완성을 포함한 해상 및 육상 플랜트가 포함됩니다.

    석유는 육상으로 옮겨져야 하는 관계로 운송 전에 분리 작업이 필요합니다. 1차 및 2차 분리 단계는 일반적으로 가스 흐름, 물 흐름 및 오일 흐름의 3단계로 분류됩니다. 가스 이동은 파이프라인을 필요로 하며, 이동하기 전에 상류 공정에서 분류 공정을 거치게 됩니다. 액체는 탱크 또는 파이프라인에 넣고 운송을 하므로 정확한 레벨 측정이 가능한 레벨계가 필요합니다.

    See More
  • 오일 및 가스

    Yokogawa는 해상 및 육상 시설에서 파이프라인, 터미널 및 심해 운전에 이르기까지 석유 및 가스 사업의 모든 부분에서 풍부한 경험을 보유하고 있습니다. 우리는 안전을 강화하고 정확하고 신뢰성 있는 운전을 보장하며 플랜트 효율을 높이는 솔루션을 제공합니다.

    See More

Top