Stop monitoring and recording on DAQLOGGER, then perform steps 1 to 3.
On GateMX/MW, click the Acquire button of the corresponding MW100 to get the MW100's information.
In DAQLOGGER manager, use "ENVI" on the Gate to perform automat...
I'm using an old version of the product, but can I upgrade to a DAQWORX edition of the software?
(ns-faq-daqworx-13026-select)
Yes, an inexpensive release upgrade kit is available.
Into what units does DAQLOGGER automatically divide files during recording?
(ns-faq-daqworx-13025-spec)
Files can be automatically divided by number of data, day, or hour. Also, with the latest versions (R7.08 or later), files can be divided by month.
What communication formats are compatible with DAQLOGGER?
(ns-faq-daqworx-13005-connect)
Ethernet, RS-232C, and RS-422A/485.
After connecting two units of the DX100P/DX200P to GateDX-P, how can I connect to DAQLOGGER?
(ns-faq-daqworx-13055-connect)
The following shows you how to assign 2 instances of Gate to DAQLOGGER. Launch GateDX-P, then click the ENVI button in DAQLOGGER manager.
After GateDX-P starts, click the ENVI button in DAQLOGGER manager.
Assign 2 Gates
Click the address field o...
It is the DAQLOGGER time, in other words, the time on the PC.
How can I view historical data files (*.mld) and reports (*.rbi) from DAQLOGGER on a Windows 10 PC?
(ns-faq-daqworx-13077-spec)
Use the latest version of SMARTDAC+ Standard Universal Viewer.
I see the following log in the DAQLOGGER logs: "LackData recNo:01 num=2." What do "LackData" and "num" mean?
(ns-faq-daqworx-13071-spec)
When logging in DAQLOGGER, “LackData” appears in the logs if some data is missing, and “num” is the number of missing data.
With DAQWORX programs, even if the licenses are different, you cannot run multiple instances of the same software on the same OS. If using two GateMODBUS licenses, please use two different PCs, configuring them as follows.
1st PC: GateMODBUS,DAQLOGGE...
When I try to copy data files being recorded on DAQLOGGER to another folder, recording stops.
(ns-faq-daqworx-13058-spec)
When data files are being recorded, the OS prevents them from being accessed by other software. If DAQLOGGER attempts to write to a file being copied, it will be prevented from doing so. Do not copy files being recorded.
Can I create hourly and daily reports on DAQLOGGER and automatically print them out ?
(ns-faq-daqworx-13023-spec)
You can create them with the Report function, but you cannot print them out.
After I automatically convert to Excel format in DAQLOGGER I can't open the file.
(ns-faq-daqworx-13024-spec)
Check the number of data and tags. Excel's maximum worksheet size is 65536 rows by 256 columns. Set it up so that the number of data along the time axis is 65536 or less, and the number of tags is 250 or less.
How can I output an alarm beep on DAQLOGGER?
(ns-faq-daqworx-13022-spec)
Open the alarm window, then check Alarm sound in the Monitor menu.
Can I send alarm occurrences via e-mail?
(ns-faq-daqworx-13008-spec)
Yes. Set this up in the event processor.
Can I connect multiple products to DAQLOGGER?
(ns-faq-daqworx-13007-spec)
Yes. Up to 32 units can be connected.
Can I connect with Modbus instruments?
(ns-faq-daqworx-13006-connect)
By using GateModbus, you can acquire data from Modbus devices on DAQLOGGER.
In the DAQLOGGER screen, can I display data from one MX100 and one DA100?
(ns-faq-daqworx-13011-spec)
MX100 → GateMX/MW or MXLOGGER → DAQLOGGER
DA100 → DAQLOGGER
with the above you can load both data on DAQLOGGER, but it will take at least one second.
Can I execute recording start on a server side DAQLOGGER from a client side DAQLOGGER?
(ns-faq-daqworx-13009-spec)
Yes. Use the remote controller function.
What are the differences between the DAQLOGGER and DAQEXPLORER recording functions?
(ns-faq-daqworx-13017-spec)
Generally, the recording functions differ as follows.
On DAQLOGGER, data from multiple products is acquired and recorded together at the time of the PC, so it has a degree of synchronicity.
With DAQEXPLORER, files are recorded at the time on the ...
What rules apply regarding the strings used for DAQLOGGER TAG, TAG comment, and GR name?
(ns-faq-daqworx-13020-spec)
The TAG numbers cannot be changed. They are fixed from TAG0001 to TAG1600. The TAG comment can be up to 16 half-width alphanumeric characters, and the GR name can be up to 8.
How many data can be displayed along the time axis in DAQLOGGER's real time trend display?
(ns-faq-daqworx-13021-spec)
3600. Data beyond that are invisible.
When acquiring data on DAQLOGGER, can I also view the screen on another PC?
(ns-faq-daqworx-13019-spec)
Yes, you can if you use the DAQLOGGER client.
After you start scanning, you have to start logging too. After you start logging, the files will start to be created at the specified date/time.
Unfortunately you will need to stop DAQLOGGER. When you rescan, the changed alarm values will apply.
I'm using DAQLOGGER and an old recorder. Can I connect the SMARTDAC+ GM10 to DAQLOGGER?
(ns-faq-gm-14024-spec)
No.
Consider the GA10 Data Logging Software.
The GA10 can connect with DAQLOGGER.
For details, see GA10 General Specifications (GS 04L65B01-01EN) "Connectable Devices and Software".
...
When viewing MXLOGGER from DAQLOGGER, the MXLOGGER data is distinguished by the MXLOGGER system number. The system number is set automatically according to the MX scan interval and unit. When specifying an MXLOGGER on DAQLOGGER, if you specify a syst...
Can I acquire µR10000/µR20000 data on a PC using DAQLOGGER?
(ns-faq-daqworx-13010-spec)
Yes, by using GateµR along with DAQLOGGER.
My PC shut down while DAQLOGGER was running, and now I can't communicate with the DX1000. What should I do?
(ns-faq-daqworx-13059-connect)
If DAQLOGGER stops while communicating with the DX1000, depending on the timing, the DX1000 might enter a response wait state and be unable to receive any other commands. With apologies, please turn OFF the DX1000 and restart DAQLOGGER.