When I set the user parameter unit to EU or EUS on the custom computation building tool, I can't input a value in the initial value cell.

Since the custom computation building tool cannot hold AINn and PVn scale data, the limit check cannot be performed on the input value when you select EU or EUS for the unit. Therefore, it prevents you from entering a value. If the unit is set to EU or EUS, after setting and downloading a unit on the custom computation building tool, set the user parameter value on the controller main unit or parameter setting tool.