For SMART 920 wireless communication between the GX70SM wireless input unit and the parent unit (SMARTDAC+ GX20/GP20, GM10), what status conditions are included in "Wireless Input Unit Error" under "Device Status" for relay contact output?

The following statuses and sub-statuses are covered by Wireless Input Unit Error:

  • Status CAUTION, sub-status LOW_BATTERY: Battery abnormality.
    *The battery of the GX70SM is low
  • Status CAUTION, sub status DEAD_BATTERY: Battery abnormality
    *The battery of the GX70SM is dead
  • Status CAUTION, sub status UNIT_CHANGE: Device change occurred
    *Only occurs with the /AS option (the advanced security function)}
    *A GX70SM with a different serial number from the reconstructed GX70SM is connected
  • Status ERROR, sub-status ERROR: Malfunction
    *Malfunction of the GX70SM *1
    *1 :Malfunction of the GX70SM refers to the following conditions:
    • Abnormal settings and calibration values
    • A/D abnormality
    • Hardware, CPU abnormality
    • Flash/FRAM sum abnormality
    • Mode setting abnormality
    • Burnout
  • Status FAILED, sub-status: Communication lost
    *Communication with the GX70SM has not occurred for about 90 seconds