Introduction
A unique feature of the EJX-A series is the Status Output option (/AL). This option provides an on / off output signal separate from the 4 to 20 mA analog single. The on / off output signal is driven off the user configurable high and low alert values. The status output can be assigned as any combination of the high or low alert values of the Input Pressure, Input Static Pressure, or Capsule Temperature.
Uses for the Status Output:
- Tank Level - Eliminates a level switch
- Capsule Temperature - Remote location health monitoring (Adjacent equipment, Heat tracing, or process runaway)
- Static Pressure - Monitor pumps, valves, or tank blankets
- Flow Limits - Alarm at low or high flow conditions
- Diagnostics - Monitor other process conditions without the need or expense of additional devices
The Status Output employs a 5% (50C for temperature) buffer value to avoid output chattering.
See Figure 1.
![]() |
![]() |
Status Output for Low Alert Value | Status Output for High Alert Value |
Figure 1: High and Low Alerts for Status Output |
Applicable Models
- EJA-E Series: Not available
- EJX-A Series: Available as an option for all models except EJX910A and EJX930A.
Specifications
Output Type: Transistor output (Sink type)
Contact Rating: 10.5 to 30.0 VDC 120 mA DC (Max)
Wiring
Figure 2: Sample Wiring of Local Visual Alarm or Audio Alarm
Programming
The Status Output is driven off the Process Alerts. Process Alerts are available whether the transmitter has the Status Output option or not.
Setting Process Alerts
Process Alerts are used to give special Alerts to the Control System of certain critical process variables. The transmitter needs to have the variable monitored and the value for alarm defined. This can be done using DTM Works in FieldMate.
Setting Status Output
Once the Process Alerts are set, the Status Output can also be set-up using DTM works in FieldMate.
Digital Output Read Only. Displays Enable / Disable status of Digital Output.
DO Select Selects which variable for the Status Output to react to.
DO Signal Type Selects if the contact in On or Off when the selected process alarm is triggered.
Although FieldMate is highlighted here, any Hart Communicator has access to these functions. Refer to the User's Manual for the HART programming tree.
This function is available for HART 5 and HART 7.
Setting when Shipped
Status Output is OFF when shipped.
BRAIN PROTOCOL
The features described in this FieldGuide are also available for EJA-E and EJX-A transmitters with BRAIN Protocol communication. Please refer to the User's Manual for details.
Productos y Soluciones Relacionadas
-
EJX910A
Este transmisor mide con precisión la presión diferencial, la presión estática, y la temperatura del proceso; además utiliza estos valores en un ordenador de flujo de alto desempeño para ofrecer Flujo Másico que está compensado.
-
EJX930A
Está diseñado específicamente para aplicaciones de alta presión estática, este transmisor mide con precisión la presión diferencial, la presión estática, y la temperatura del proceso; además utiliza estos valores en un ordenador de flujo de alto desempeño para ofrecer Flujo Másico que está compensado.