pH Monitoring of Pulp Stock

다운로드 (292 KB)

Introduction

Continuous technology improvement is ongoing in the pulp & paper industry to obtain the best possible performance. Problems at the wet end (stock preparation) can rarely be corrected downstream. That is why monitoring and controlling pH in pulp stock is critical to the paper making process. Essentially, at every stage in the manufacture of paper, correct pH values play a vital role.

Process

The Kraft Process is a cyclical, self-sustaining process. As a result of the process, a byproduct called black liquor (tall oil) is formed. There are two different forms of pulping process: Chemical pulping and Mechanical Pulping. Maintaining proper pH measurements in the stock preparation is important for producing quality finished product. The stages will vary depending on the type of paper that the end product will require; however, each will have some form of refining, chemical addition and screening of the pulp.

Typically the pulp is diluted and passed thru a refiner. The pH is typically maintained >8 pH. Inaccurate pH measurement at the first refiner can have an effect on the strength of the pulp. The purpose of the refiner is to shred and flatten the pulp. After the stock passes thru the refiner it enters a mixing tank where chemical additives are introduced. Once the correct pH is achieved the stock enters the machine chest, where the consistency of the stock is then set. Once the consistency is accurate, the pH is monitored again before the stock is pumped thru the final screening before the stock reaches the headbox. The headbox is the final point to ensure proper pH of the pulp stock before the paper machine. Once the stock enters the paper machine it cannot be corrected.

Stock Preparation

Product Recommendations

Measurement System

FLXA202/FLXA21, FLXA402Transmitter/Analyzer

  • 2-wire FLXA202/FLXA21 pH/ ORP measurement system
  • 4-wire FLXA402 pH/ORP measurement system

Option 1:

Model PH87Yokogawa has extensive experience dealing with the clogging and fouling problems that occur with pH measurements in paper mills. This has led us to select the Model PH97/DP sensor which has a solid state reference resistant to clogging and fouling. The PH97 is designed as a replaceable 4-1 sensor used in conjunction with the Model PH87 retractable assembly. The PH97 includes a pH (glass0 electrode, solid state reference electrode, solution ground and a Pt 1000 temperature element. All these components are sealed in a rugged Ryton™ body.

The Model PH87 assemblies are constructed of chemically- resistant titanium and include blowout safety protection utilizing a flared tip design which provides a metal to metal stop during retraction. Integral junction boxes are provided for simple installation and wiring. The retractable assembly is suitable for removal from a process line or vessel at pressures up to 70 PSI without interrupting the flow or draining the tank. The PH87 comes different lengths to simplify proper insertion in the process line or tank.

Option 2:

Model PH18Another alternative Yokogawa offers is the model PH18 differential pH sensor that is constructed of an enamel coated steel rod. The PH18 consists of a pH sensitive enamel and a sodium ion enamel combined with a integral temperature element, to form a probe without internal solutions. Therefore, the PH18 contains no reference electrode or junction that could become clogged or give way to fouling. This sensor has very little maintenance, once it is initially installed and calibrated in place for the first time.

Option 3:

Pt1000

Another alternative Yokogawa offers to the model PH18 differential pH sensor is the SC24V cation differential pH sensor. The reference portion of the SC24V is made entirely of a glass which provides a mV output corresponding to the Cation concentration of the process or solution it is in. Therefore, there is no liquid junction to be coated or clogged and no path for the process to affect the electrolyte or the internal Ag/AgCl element. This sensor has very little maintenance, once it is initially installed and calibrated in place for the first time.

Option 4:

Another alternative Yokogawa offers is the all-in-one style FU20/FU24. The wide body sensor holds four separate measuring elements in one unbreakable and chemical resistant PPS 40GF (Ryton™) body. Installation is simple with the integrated industrial 3/4" or 1" tapered thread connections.

FU20/FU24

Note: For additional information or assistance on this application, please contact the Yokogawa Analytical Product Marketing.

Related Products & Solutions

  • 2-Wire Transmitter/Analyzer FLXA202

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

    See More
  • Differential pH/ORP Sensors

    양이온 차 pH 및 ORP 센서는 기존 센서가 비효율적인 어려운 어플리케이션을 위해 설계되었습니다. 여기에는 전해액 공정 및 치즈 제조와 같은 다양한 어플리케이션에서 염수 용액과 같은 측정이 포함됩니다.

    See More
  • Digital SMART SENCOM™ Adapter, SA11

    Reusable SMART adapter, requiring only the analog sensor to be disposed of when it reaches the end of its lifetime. With the SENCOM 4.0 platform, Yokogawa delivers reduced costs and waste while contributing to its long-term business goals of a sustainable future for all.

    See More
  • pH and ORP Analyzers

    pH와 ORP 미터, 분석계 및 전송기는 수질/제품 품질을 보장하고 유출물 배출량, 배치 중화, 펄프 스톡, 세정기, 냉각 타워, 화학, 폐수 처리 및 기타 여러 어플리케이션의 연속 공정 모니터링에 사용합니다.

    See More
  • pH and ORP Sensors

    pH 전극 및 센서는 pH 측정의 감지 부분입니다. Retractable, flow-though, 침적 및 직접 삽입을 포함한 다양한 설치 옵션이 있습니다.

    적절한 pH 전극 / 센서 선택은 최적의 측정 결과를 위해 중요합니다.

    See More

Top