Q:
I'm connecting a UT with CC-Link communication to another downstream UT via RS485 communication (Modbus master function). However, the RS485 communication terminal of the UT with CC-Link communication is a 2-wire system, and that of the other is a 4-wire system. How should I make the connection in this case?
A:
Wire the UTs to each other using a 2-wire system. For the 4-wire system terminals, short SDB(+) and RDB(+), and SDA(-) and RDA(-).
Productos y Soluciones Relacionadas
-
UM33A
The UM33A is a digital indicator with alarms provides up to 9 alarms outputs and input correction function (PV bias, Polygonal line approximation, polygonal line bias). Also, 24 VDC sensor power supply is available as an option.
-
UP35A/UP32A
The UP35A is a program controller with available 4 patterns and 40 segments (max.) and multi-channel contact I/O. It also includes a ladder sequence function. The UP32A is a compact program controller with up to 4 patterns and 40 segments available. It also includes a ladder sequence function.
-
UP55A
The UP55A is a newly-released 1/4 DIN sized program controller provides up to 30 program patterns, and simultaneous monitoring of 8 PV events, 16 time events, and 8 alarms. Also a ladder sequence function is included as standard.