Yes, if using a UTAdvanced series instrument with the RS-485 communication option. Set the RS-485 protocol on the main unit to 8 (MBRTU: Modbus RTU). The initial value is 8. Select RS-485 in the LL50A communication execution screen, and make the communication conditions and addresses the same as on the main unit.
Related Products & Solutions
-
Advanced Application UT75A
Temperature Controller with increased monitoring and operating capabilities
-
LL50A
Build and set parameters and ladder programs with advanced software
-
Mid-level UT55A/UT52A
Increase monitoring and operating capabilities
-
UM33A
Digital Indicator with 9 alarms outputs and input correction function
-
UP35A/UP32A
Program Controllers with 4 patterns, 40 segments, and ladder sequence functions
-
UP55A
Program controller with 30 patterns, simultaneous monitoring, and ladder sequence function
-
UT32A-D
Digital Indicating Controller with selectable 2-loop control and intuitive design
-
UT35A/UT32A
Increase monitoring and operating capabilities