Can you tell me how to get the measurement accuracy when measuring 0 to 1000°C with a type K thermocouple? I selected input type K2 (-270.0 to 1000.0).

Per the specifications, the accuracy of type K at 0°C or higher is ±0.1% ±1 digit. The measuring range in this case is that of the selected input type, -270.0 to 1000.0. You can calculate the accuracy as follows.
±0.1% of 1270°C = 1.27°C, plus 0.1°C of 1 digit = 1.37°C.

Related Products & Solutions

  • UM33A

    Digital Indicator with 9 alarms outputs and input correction function

  • UP35A/UP32A

    Program Controllers with 4 patterns, 40 segments, and ladder sequence functions

  • UP55A

    Program controller with 30 patterns, simultaneous monitoring, and ladder sequence function

  • UT32A-D

    Digital Indicating Controller with selectable 2-loop control and intuitive design