Can I set the PV display to -100 with 20 mA input, and to 0 with 4 mA input?

In this case, 20 mA is the minimum value of PV input, and 4 mA is the maximum. In the setup parameter PV menu, set RH=4.00 and RL=20.00 (the input range maximum and minimum values). For the PV input scale max, min, and decimal place, set SH=0, SL=-100, and SDP=0. SH must be greater than SL.